38
12
Specific
12V/24V
36V/48V
12V/24V
36V/48V
0H
0H
13
Specific
12V/24V
36V/48V
12V/24V
36V/48V
0H
0H
14
OFF
Programming with CAN-Bus
15
OFF
Programming with UNI-DISPLAY-R
Some specific settings are possible
–
please consult us.
(*) Voltage on + BAT with 10% of the rated current and a tolerance of +/- 1%.
(
**
)
REFRESH is not advised for certain types of AGM batteries
(***) Battery Management System
3.3.3
Programming field 2 : Select special mode
Setting
REFRESH
mode
BOOST
mode
0
OFF
OFF
1
OFF
ON
2
ON
OFF
3
ON
ON
-
The BOOST function allows a faster charging of the batteries. This function is timed in time (see section 3.3.2.)
And is automatically inhibited if the battery is charged: shutdown of the BOOST for a battery current <20% of the
nominal current of the charger / converter (2A in the case of the Lithium curve Iron Phosphate with BMS with a
minimum time of 10 minutes).
-
The REFRESH function allows to apply a voltage step periodically to maintain the battery, to promote its
equalization and thus prevent possible sulfating.
3.3.4
Programming field 3 : Select CAN address
This address is valid only for Cristec CAN Protocol
Setting
CHARGER /
CONVERTER_Frame1
CAN address
Setting
CHARGER /
CONVERTER_Frame1
CAN address
0
0x0002 9000 master A
8
0x0002 9008 slave A2
1
0x0002 9001 master B
9
0x0002 9009 slave B2
2
0x0002 9002 master C
10
0x0002 900A slave C2
3
0x0002 9003 master D
11
0x0002 900B slave D2
4
0x0002 9004 slave A1
12
0x0002 900C slave A3
5
0x0002 9005 slave B1
13
0x0002 900D slave B3
6
0x0002 9006 slave C1
14
0x0002 900E slave C3
7
0x0002 9007 slave D1
15
0x0002 900F slave D3
It is possible to parallel several modules (one master A with a maximum of three slaves A1, A2 et A3), all the
slaves X will synchronize with the master X. Each module must have a different address.