Grounding requires the following:
•
Grounding wires that are insulated and at least equal in size to the phase
conductors.
•
Ground impedance less than 2 Ohms.
•
A single point and dedicated ground.
•
Each system load (such as platesetter, host) is fed through an isolated ground
outlet and has a separate ground, as well as neutral and phase line of equal size
wire.
Note:
Chained neutrals and grounds are not permitted