CHART 1
BALLAST (in cubic yards)
BASIN
I.D.
BASIN HEIGHT
48”
60”
72”
84”
96”
108”
120”
144”
24”
0.30
0.38
0.46
0.53
0.61
0.69
0.78
0.93
30”
0.48
0.60
0.71
0.84
0.96
1.08
1.21
1.45
36”
0.70
0.88
1.03
1.21
1.39
1.57
1.75
2.10
42”
0.94
1.19
1.42
1.66
1.90
2.15
2.39
2.87
48”
1.24
1.56
1.85
2.17
2.48
2.80
3.11
3.74
60”
1.88
2.38
2.88
3.37
3.86
4.36
4.85
5.84
CHART 2
DIRECT BURIAL REQUIREMENTS
PUMP MODEL
DIRECT BURIAL CABLE REQUIRED FOR PUMP POWER
ALL SGV 2HP PUMPS
12/4
ALL OGV & SGPC PUMPS
12/3
DUPLEX LEVEL CONTROL
DIRECT BURIAL CABLE REQUIRED FOR LEVEL CONTROL
FloatTREE, or UltraSWITCH and Pumps
with No Pump Sensor
18/6
IMPORTANT!
Direct Burial Cable
MUST
be
“UL Approved, Type TC ROUND”.
Flat type UF cable
WILL NO WORK.
Use of it will
VOID WARRANTY.
Conductor sizes based on maximum 300 Ft. length. Consult factory for longer lengths.
CHART 3
INLET SPECIFICATIONS
INLET PIPE SIZE
HOLE SAW SIZE
FLEXIBLE INLET COLOR
1.25” - SCH40
3”
Black
1.50” - SCH40
3”
Black/Red
2.00” - SCH40
3”
Black/Blue
3.00” - SCH40
4”
White
4.00” - SCH40
5”
Grey
6.00” - SCH40
7”
Black
4.00” - SDR35
5”
Maroon
6.00” - SDR35
7”
Yellow
(*) Consult factory for available source or alternative tool.
CORD GRIP CHART
NPT SIZE
DRILL SIZE
1/2
23/32” (.718”) Dia.
3/4
59/64” (.921”) Dia.
Grip size is found on hex flat of cord grip.