- 5 -
I - PRESENTATION
1 - DESCRIPTION
Standard description:
wall mounted condensation
boiler for hot water heating, sealed combustion cir-
cuit, pre-mixing burner with air-gas supply, and
linear power modulation connecting combustion
product types B
23
, C
13
, C
33
, following EN 483
(04/00)
The THI boiler is pre-set in the factory for natural
gas H (G20) or propane (G31) depending on the
model.
This boiler comprises all the necessary accessories
for the correct working of a water based central hea-
ting circuit specifically:
- one boiler comprising:
• a high performance double walled condensa-
tion exchanger,
- a pre-mixing burner, with stainless steel refracto-
ry grate,
- a variable speed 230 Volt fan controlled by the re-
gulator,
- a 230 Volt two way gas valve controlled by the air
pressure,
- electronic regulation which ensures power modu-
lation depending on the demands for heating or
DHW (LMU control unit),
- an outside sensor,
- a circulating pump,
- a 3 bar safety-valve,
- a gas conversion set (
to
propane
from
natural gas).
OPTIONAL:
- Horizontal flue kit (C
13
) allowing the boiler to be
connected to a straight horizontal flue.
- Accessories for horizontal connection of the boi-
ler (C
13
) - (extensions, elbows etc.).
- Flue adapter (C
33
) allowing the boiler to be con-
nected to a vertical flue.
- Accessories for vertical connection of the boiler
(C
33
) - (terminal, extensions, elbows etc.).
- Adjustment as a function of the room temperature
(REG 73).
- 2nd heating circuit kit allowing the connection of
a secondary heating circuit (REG 126).
- Clip-in kit secondary circuit allowing the connec-
tion of a secondary heating circuit.
- Clip-in communication LPB kit used for cascade
or multi-circuit installations (REG 130).
- Clip-in programmable relay kit allowing a secon-
dary pump to work in parallel (REG 127).
- Control unit ZHTi 46 (REG 129) controlling an ad-
ditional heating circuit.
- Control unit ZHTi 47 (REG 128) allowing cascade
management for two boilers.
-
- Domestic hot water production system (type BS).
2 - RANGE
Models
Functions
Combustion products
connection
THI 10-50 C
Only heating
Chimney conduit (B
23
)
Horizontal flue (C
13
)
Vertical flue (C
33
)
Содержание THI 10-50c