Determine the Depth of Your Welll
Shallow wells are less than 25 feet to water; deep wells
are up to 70 feet to water. Tie a small but heavy weight
to the end of a piece of string (be sure there is enough
string; some wells are very deep). Lower the weight into
the well until it reaches the bottom. Take up the slack
and mark the string at ground level. Pull the weight out
of the well and measure from the bottom of the weight
to the ground level mark. This is the depth of your
well. Subtract five feet from the depth of your well. This
number should not exceed the maximum rated depth for
your pump. If it does, it will greatly hinder or prevent the
proper operation of the pump.
Correctly Select Your Pump Voltage
Risk of electric shock . Can shock, burn or
kill. Disconnect power to pump before working on pump
or motor. Disconnect pump from power source before
changing the pump voltage.
To change the voltage, the selector switch is located
underneath the plastic access cover on top of the motor.
To access the switch, remove the eight screws holding
the plastic cover. To change the voltage setting, slide the
switch as shown until desired voltage is visible on the
switch. The voltage number that appears is the voltage
setting for the pump. Be sure the switch is completely
engaged. Replace the cover and secure it with the
eight screws.
Wiring Your Pump
Risk of electric shock . Can shock, burn or
kill. Disconnect power to pump before working on pump
or motor. Disconnect pump from power before servicing
or handling pump.
Remove the cover from the pressure switch. Connect the
bare copper ground to the ground screw in the pressure
switch. Connect the power supply to the terminals
labeled “From Line" in the diagram below.
Piping
Plastic PVC pipe is shown in the illustrations, but
galvanized steel pipe may be used if desired. All
piping must be clean and free of all foreign matter to
prevent clogging.
ALL JOINTS AND CONNECTIONS IN THE WELL
ASSEMBLY MUST BE AIRTIGHT. Even a pinhole leak
will prevent the proper operation of the pump (this is the
most common problem). Use PTFE pipe thread sealant
tape on all threaded joints unless specified otherwise.
1 15
230
1 15
230
VOLTAGE SELECTION DIRECTIONS
Warning!
Disconnect pump from power
source before servicing or
handling pump.
Be sure that incoming power
supply is same as voltage
selector switch setting.
To change voltage settings
slide switch as shown
until desired voltage is
visible on switch.
Be sure switch is completely
engaged.
Replace capacitor housing cover
and secure cover with screws.
Do not overtighten screws.
22700A375
Wiring Chart – Recommended Wire and Fuse Sizes
Model
Motor HP
Volts
Nameplate
Amps
Branch Fuse
Rating Amp
Distance In Feet(Meters) From Motor To Supply
0 - 100
(0 - 30)
101 - 200
(31 - 61)
201 - 300
(62 - 91)
301 - 400
(92 - 122)
AWG Wire Size (mm²)
CLTS5
1/2
115/230
8.5/4.2
15/15
14/14 (2/2)
12/14 (3/2)
10/14 (5.5/2)
8/14 (8.4/2)
CLTS10
1
12.0/6.0
20/15
12/14 (3/2)
10/14 (5.5/2)
8/14 (8.4/2)
6/14 (14/2)
CL520
1/2
7.0/3.5
15/15
14/14 (2/2)
12/14 (3/2)
10/14 (5.5/2)
10/14 (5.5/2)
CL100
1
11.0/5.5
20/15
12/14 (3/2)
10/14 (5.5/2)
8/14 (8.4/2)
6/14 (14/2)
Ground
Connections
To Motor
From Line
5907 1108
Installation 4