Troubleshooting 11

Problem

Check

Corrective Action

Pump starts too frequently .

Leaks in system.

Check all tank connections with 

soapsuds for air leaks. Check 

plumbing for leaks.

System must be air and water tight.

Pressure switch.

Check for defective switch or switch 

out of adjustment.

Re-adjust or replace pressure switch.

Tank waterlogged.

Pre-charged tanks; check tank pre-

charge air pressure, check for leak in 

bladder.

Pre-charge tanks: adjust air pressure 

to 2 PSI (13.8 kPa) less than pump 

cut-in pressure (when there is no 

water pressure on system). Replace 

bladder if necessary.

Air over water tanks: check for air 

leaks. Check Air Volume Control 

(AVC). Check air pressure valve 

operation.

Air over water tanks: repair or replace 

tanks; replace air pressure valve if 

necessary.

Leak in drop pipe.

Raise drop pipe one length at a time 

until water stands in pipe.

Replace pipe above that point.

Pressure switch too far from 

tank.

Measure distance from pressure 

switch to tank.

Move switch to within one foot (.3m) 

of tank.

Little or no water delivered .
Bleeder orifice check valve 

stuck or installed backwards 

(standard tank only).

Examine valve.

If stuck, free valve; if installed 

backwards, reverse it.

Low water level.

Determine lowest water level in well 

while pump is running and compare 

to pump depth setting.

Lower pump further into well (but 

at least 5’ (1.6m) above bottom 

of well). Throttle pump discharge 

until discharge equals recovery rate 

of well. 

 NOTICE Running pump while 

airlocked can cause loss of prime and 

seriously damage pump.

Low voltage.

Check voltage at control box with 

pump running. Check incoming wire 

size and drop cable size against 

Cable Sizing tables.

Install larger wire from meter to 

control box. Install larger wire from 

control box to pump. If necessary, 

have power company raise supply 

voltage.

Plugged intake screen.

Pull pump and check condition of 

screen.

Clean or replace as necessary.

Check valve at pump 

discharge stuck.

Pull pump and examine check valve.

Free check valve.

Worn impellers and diffusers.

Make sure system is clear of 

obstructions and pump is in solid 

water and operation normal.

Replace pump.

Air or milky water discharge from faucets .

Gas in well water.

Check for presence of gas in well 

water.

Remove bleeder orifices; plug tees. 

Be sure plugged tees do not leak. 

If necessary, separate gas from air 

before it enters pressure tank.

Air volume control not 

working (standard tanks 

only).

Make sure ports and ball check valves 

are clear.

Replace control if necessary.

Содержание 102890199

Страница 1: ...v 01 06 17 Installation Operation Parts For further operating installation or maintenance assistance Call 800 535 4950 English Pages 2 12 Instalaci n Operaci n Piezas Para mayor informaci n sobre el f...

Страница 2: ...n must meet United States National Electrical Code Canadian Electrical Code and local codes as applicable for all wiring Disconnect electrical power supply before installing or servicing pump Make sur...

Страница 3: ...rge as wires carrying current to motor See Table 1 for recommended fuses and also see Cable Splicing Motor is supplied with copper ground wire Splice to copper conductor that matches motor wire size s...

Страница 4: ...rload trips look for 1 Shorted capacitor 2 Voltage problems 3 Overloaded or locked pump NOTICE Use only control box specified for your pump Make sure motor and control box match Table 3 Failure to do...

Страница 5: ...Make four passes with the tape when finished you should have four layers of tape tightly wrapped around the wire Press edges of tape firmly down against the wire see Figure 5 NOTICE Since the tightly...

Страница 6: ...ed in designated location Most submersible motors will include a ground lead for connection Other motors will have designated location on motor bracket 4 Use only submersible cable supplied by pump ma...

Страница 7: ...s relief valve between pump and tank NOTICE Allowing pump or piping system to freeze may severely damage pump and will void warranty Protect pump and entire piping system including pressure tank from...

Страница 8: ...on Submersible motor control 3 wire models Electrical disconnect Pressure gauge Air volume control Pressure switch To house service Gate valve Relief valve 2 ft 6 m See table 6472 1111 Figure 11 Typic...

Страница 9: ...s Electrical disconnect Pre charged tank Pressure switch Pressure gauge To house service Relief valve Union Gate valve 6471 1111 Figure 12 Typical Pre Charge Tank Installation Cut In PSI Cut Off PSI P...

Страница 10: ...ontrol box Check control box wiring diagram against incoming power hookup Reconnect leads to match wiring diagram in control box cover Check drop cable color coding Reconnect drop cable so cable color...

Страница 11: ...ee valve if installed backwards reverse it Low water level Determine lowest water level in well while pump is running and compare to pump depth setting Lower pump further into well but at least 5 1 6m...

Страница 12: ...l rental applications Sewage Pumps DO NOT return a sewage pump that has been installed to your retail store Contact CountyLine Customer Service Sewage pumps that have seen service and been removed car...

Страница 13: ...de instalar la bomba o de realizar tareas de reparaci n y mantenimiento Verifique que la tensi n de l nea y la frecuencia del suministro de corriente el ctrica coincidan con la tensi n y la frecuenci...

Страница 14: ...alme del cable El motor viene equipado con un cable de cobre de puesta a tierra Empalme este cable a tierra a un conductor de cobre que concuerde con el tama o del hilo del motor especificado en los T...

Страница 15: ...se dispara verifique que no haya 1 Un capacitor en corto circuito 2 Problemas de tensi n 3 Bomba sobrecargada o bloqueada AVISO Use solamente la caja de control dise ada para usar con la bomba Aseg r...

Страница 16: ...ase la cinta cuatro veces Es decir cuando termine tendr cuatro capas de cinta envueltas firmemente alrededor del cable Presione los bordes de la cinta firmemente contra el cable consulte la Figura 5 A...

Страница 17: ...otores sumergibles incluyen un conductor a tierra para la conexi n Otros motores tendr n un lugar designado en el soporte del motor 4 Use solamente cables sumergibles suministrados por el fabricante d...

Страница 18: ...tanque AVISO Si se permite que la bomba o el sistema de tuber as se congelen existe el riesgo de provocar da os graves en la bomba y esto invalidar la garant a Proteja la bomba y todo el sistema de tu...

Страница 19: ...que est ndar Distancia de la v lvula de retenci n al orificio de purga superior Capacidad del tanque en galones l distancia en pies m 42 159 2 6 82 310 4 3 9 120 454 2 5 1 5 Uni n V lvula de alivio V...

Страница 20: ...ol box 3 wire models Electrical disconnect Pre charged tank Pressure switch Pressure gauge To house service Relief valve Union Gate valve 6471 1111 Figura 12 Instalaci n t pica para un tanque de presi...

Страница 21: ...n de corriente el ctrica de entrada Vuelva a conectar los conductores para que coincidan con el diagrama de cableado en la tapa de la caja de control Verifique los c digos de color del cable de segre...

Страница 22: ...nivel del agua Determine el nivel m s bajo de agua en el pozo cuando la bomba est marchando y comp relo con la graduaci n de profundidad de la bomba Baje la bomba a mayor profundidad en el pozo pero...

Страница 23: ...productos utilizados en aplicaciones comerciales o de alquiler Bombas cloacales NO devuelva una bomba cloacal que se haya instalado a su tienda minorista Comun quese con el Departamento de Atenci n al...

Страница 24: ......

Отзывы: