69
AGUADENS
COSMOGAS
ATTENTION !!!
The modification of these parameters could cause the appliance, and therefore the plant, to malfunction.
For this reason only a technician that has the awareness and in-depth knowledge of the appliances can modify
them.
To access this menu, move the microswitch as stated in figure 6.5 detail “B”.
11 - ENGINEERS TEST MODE
Parameter
Parameter Description
M.U.
Setting range
Factory value
Customised
value
3002
Selection type
From 50 to 55
See figure 6.7
3012
Domestic hot water operating
mode
/
0 =
DO NOT USE
;
1 = Storage tank with temperature sensor;
2 = Storage tank with thermostat;
3 =
DO NOT USE
;
4 =
DO NOT USE
;
5 = Instantaneous with turbine;
5
3013
No function
/
/
/
3014
Instantaneous domestic hot
water pre-heat
/
OFF = No pre-heat
ON = With pre-heat OFF
OFF
3015
No function
/
/
/
/
3016
No function
/
/
/
/
3020
Domestic hot water flow rate
sensor
/
0 = B;
1 = DN 8; (AGUADENS 16)
2 = DN 10;
3 = DN 15; (AGUADENS 22, 27 and 37)
4 = DN 20;
5 = DN 25;
0
3021
2nd Exhaust flue sensor (1014)
/
0 = Disabled;
1 = Enabled;
2 = Enabled with exhaust flue anti-closure
pressure switch;
1
3022
No function
/
/
/
3033
No function
/
/
/
3034
No function
/
/
/
3035
No function
/
/
/
3036
No function
/
/
/
3052
No function
/
/
/