© Corroventa Ltd.
2017.05
24 (43)
Alarms
In this screen, the machine presents identified alarms.
As soon as an alarm is identified, this is also presented
as a pop-up screen. Furthermore, as long as the error
condition remains, in the top right corner of the default
view there is an warning symbol.
The alarms presented need not be erased by the user.
Instead, as soon as the machine detects that the
functionality is again in place, the alarm will disappear
automatically.
Control Modes and Hysteresis
In addition to normal, continuous drying operation, the CTR A ES operation can be controlled by use
of its internal Relative Humidity and Temperature sensor, external hygrostat or external, networked
sensor.
When using an electronic sensor, built-in or external, the machine applies a software controlled
hysteresis to make the operation of the machine stable and prevent excessive on- and off -switching.
The table below presents the default settings of the machine. If changes are required, these can be
made under the Setup and Maintenance menu.
Control mode
Hysteresis
Setpoint position
RH
4%
Bottom
Dewpoint
2°C
Top
Mix
0.5 g/kg
Bottom
The below illustrations describe the different hysteresis settings, bottom, center and top.
Setpoint RH 60%.
Start drying= 65%
Hysteresis
5%
5 %
Bottom position
Setpoint RH 60%.
Start drying= 62,5%
Hysteresis
5%
5 %
Center position
Содержание A2 ES
Страница 1: ...A2 ES A4 ES A4 ESX ADSORPTION DEHUMIDIFIERS USER MANUAL...
Страница 39: ...Interface Map for CTR A2ES CTR A4 ES and CTR A ES Top Menu...
Страница 40: ...Sublevels Info Statistics Info Reset Info Info Info Info Info...
Страница 42: ...Create Activate Edit Edit Change...
Страница 43: ...Info Change OK Info Info...
Страница 44: ...Info Change OK...