- 43 -
Cod. 1910000001165 - nv01
English
10.3.1
Parameter table
PARAMETER TABLE
Parameter
no.
Description
Range
Default
Notes
0
Set point temp. Heat Pump
10 ~ 70°C
50°C
Editable
1
Heat Pump activation temperature
hysteresis
2 ~ 15°C
5°C
Editable
2
Heating
element
switch-off
temperature setpoint
10 ~ 85°C
55°C
Editable
(Never exceed 75 °C)
3
Heating element switch-on delay
time
0 ~ 90min
6min
t * 5 min
4
Weekly
antibacterial
cycle
temperature
50 ~ 70°C
70°C
Editable
5
Antibacterial cycle time
0 ~ 90 min
30 min
Editable
6
Defrosting time
30~90 min
45 min
Editable
7
Heat exchanger temperature for
Defrosting start
-30 ~ 0°C
-7°C
Editable
8
Heat exchanger temperature for
Defrosting end
2 ~ 30°C
13°C
Editable
9
Max defrosting cycle time
1 ~ 12 min
8 min
Editable
10
Electronic expansion valve mode
0/1
1
(0→manual, 1→auto) Keep it
always on auto
11
Overheating ΔT
-9 ~ 9°C
5°C
Always use the default value
12
Electronic expansion valve steps
in manual mode
10 ~ 47 steps
35 steps
Always use the default value
13
Antibacterial cycle start time
0~23
23
Editable (time of day)
A
Tank “IN” temperature (lower T2
probe)
-9 ~ 99°C
Current detected value.
In case of malfunction, PP1 Error Code is displayed
B
Tank “OUT” temperature (upper
T3 probe)
-9 ~ 99°C
Current detected value.
In case of malfunction, PP2 Error Code is displayed
C
Evaporator temperature
(T4 probe)
-9 ~ 99°C
Current detected value.
In case of malfunction, PP3 Error Code is displayed
D
Gas return temperature (T5 probe)
-9 ~ 99°C
Current detected value.
In case of malfunction, PP4 Error Code is displayed
E
Ambient temperature (T1 probe)
-9 ~ 99°C
Current detected value.
In case of malfunction, PP5 Error Code is displayed
F
Electronic expansion valve steps
10 ~ 47 steps
Current value of electronic expansion valve opening degree No.*10
steps
H
Antibacterial cycle recording
1~99
The number increases by a unit every time an antibacterial cycle is
completed (it resets after 99).