Xenus Plus Compact STO Manual 

16-01553 Rev 00 

Page 17 of 31 

Copley Controls 

6.6.7  24V DC Power Supply 

A constraint on the larger system is that the power supply used to provide the 24V control power to the drive 

must be a SELV or PELV type. 

6.6.8  AC Mains Over-Voltage Category 

The AC mains supplying the drive must be limited to over-voltages of Category II. The relevant standards 

assume AC mains with over-voltages per OVC III. An SPD or isolation transformer is required to  

limit over-voltages to OVC II levels. 

6.6.9  Wiring to the STO Inputs 

Electrical connections to the STO inputs must meet the requirements for fault exclusions for short circuits 

between conductors and short circuits between conductors and other conductive parts or earth or the 

protective bonding conductor. Fault exclusion requirements are given in ISO 13849-2 and IEC 61800-5-2. 

Toward this end, the STO cable connector is a crimp and poke type in order to meet the relevant fault 

exclusions. The contacts and connector provide spacing that is greater than the minimum creepage and 

clearance of 1.24 mm that is required for fault exclusion when considering the FMEDA (Failure Modes, 

Effects, and Diagnostic Analysis) of the system. 

6.6.10  Periodic Test  Requirements 

In order to meet the diagnostic coverage requirements for Cat. 3 PL d, the STO function must be checked at 

least once per year. See section 9 for specific details. 

 

Содержание Xenus Plus Compact

Страница 1: ...Xenus Plus Compact STO Manual P N 16 01553 Rev 00 September 12 2016...

Страница 2: ...ectric shock 8 3 3 Disclaimer 8 3 4 Installation Overview 9 3 5 Definitions 9 4 0 Introduction to the Xenus Plus COMPACT 10 4 1 Product Description 10 4 2 Model Overview Numbering 10 5 0 Specification...

Страница 3: ...art Up Checklist 22 7 2 1 Preliminary checks 22 7 2 2 Start Up Checklist 23 7 3 STO Status Indications 24 7 3 1 J8 AMP LED 24 7 3 2 STO Circuit Status Data Objects 24 7 3 3 CME2 Control Panel 25 7 4 T...

Страница 4: ...irective 2014 35 EU Low Voltage Directive 2006 42 EC Machinery Directive and 2011 65 EU RoHS Directive The complete EC Declaration of Conformity is available on the internet at www copleycontrols com...

Страница 5: ...mer This manual contains information on the Safe Torque Off STO feature of the Xenus Plus Compact servo drive and how it may be incorporated into an industrial motion control system While every effort...

Страница 6: ...rogrammer s Guide CMO Programmer s Guide 1 9 Reference Standards ISO 13849 1 2015 Safety of machinery Safety related parts of control systems Part 1 General Principles for Design ISO 13849 2 2012 Safe...

Страница 7: ...OVC Over Voltage Category PDS SR Power Drive Systems Safety Related PELV Protected Extra Low Voltage power supply PFD Probability of Dangerous Failure upon Demand PFH Probability of Failure per Hour...

Страница 8: ...determination as to the suitability of the Xenus Plus Compact and its STO function for use in realizing a given overall safety function The installer should be experienced in motion control and funct...

Страница 9: ...ehavior of the Xenus Plus Compact STO feature These terms are discussed and defined as follows Activate This term is used to refer to action taken that results in the safe state being entered In the c...

Страница 10: ...ame electrical specifications and differ primarily in the communications or the type of motor position feedback they support XEC and 801 1891 1893 models work with EtherCAT and XPC models work with CA...

Страница 11: ...therCAT CoE XPC CANopen ASCII and discrete I O Stepper commands 10V position velocity torque PWM velocity torque command Master encoder Gearing Camming 5 3 Power Sources Mains voltage 100 240 Vac 10 1...

Страница 12: ...abling the ability of the attached motor to produce torque force This both halts any drive induced acceleration already in process and prevents initiation of motion The expectation is that an inabilit...

Страница 13: ...TO input is driven by a 24 Vdc supply voltage switched through a safety relay Note that the STO inputs are designed to withstand input voltages to 60 Vdc to provide a measure of overvoltage protection...

Страница 14: ...Vin HI 15 0 Vdc between STO IN and STO IN STO Input De energize Voltage Level Vin LO 6 0 Vdc or open between STO IN and STO IN Input current typical STO IN1 11 2 mA STO IN2 11 2 mA Current flow is int...

Страница 15: ...61508 and ISO 13849 1 Functional Safety IEC 61508 1 2010 IEC 61508 2 2010 ISO 13849 1 2015 ISO 13849 2 2003 IEC 61800 5 2 2007 Electrical Safety Directive 2014 35 EU Low Voltage IEC UL CSA 61800 5 1...

Страница 16: ...s activated will coast to a stop unless there are other forces operating on the same load The STO function only removes torque force produced by current flow from the drive to the associated motor Tor...

Страница 17: ...e requirements for fault exclusions for short circuits between conductors and short circuits between conductors and other conductive parts or earth or the protective bonding conductor Fault exclusion...

Страница 18: ...24V power supply for the drive control power must be SELV or PELV rated 7 1 2 STO Wiring Requirements Electrical connections to the STO inputs must meet the requirements for fault exclusions for shor...

Страница 19: ...up contacts do not have the minimum 1 24 mm spacing to meet the functional safety requirements and must not be used This is an example of a cable connector that is suitable for the Xenus Plus Compact...

Страница 20: ...ay A momentary switch is wired to the safety relay reset input and is used to reset the relay at start up and after an E stop event The enable input on the drive is wired to one of the immediate INST...

Страница 21: ...s allows time for the drive to remain in an enabled state while it performs a controlled deceleration that brings the motor to a standstill before the STO function is activated preventing any torque f...

Страница 22: ...At the required periodic test intervals 7 2 1 Preliminary checks Before powering the drive and commencing with the functional safety tests check That the installation requirements given in the Xenus P...

Страница 23: ...till While keeping STO IN1 energized de energize the STO IN2 circuit and give a start command for the drive Ensure that the motor remains at a standstill Energize the STO IN2 circuit Restart the drive...

Страница 24: ...eset Red Solid Transient fault condition Drive will resume operation when the condition causing the fault is removed Green Double Blinking STO circuit active drive outputs are Safe Torque Off Green Sl...

Страница 25: ...ed Safety on the CME2 Control Panel screen gives the status of the STO function Green STO inactive Torque production in the motor is under user control Red STO active Drive outputs are Safe Torque Off...

Страница 26: ...is necessary to check 0x219D ASCII 0x139 to see if bit 0 or bit 1 is set 1 If this condition is true then the STO function is active 7 4 2 How to tell if the STO function is inactive The voltage appli...

Страница 27: ...if the user removes the cover or attempts any repairs For safety and to assure compliance with documented system data only Copley Controls shall perform repairs to the Xenus Plus Compact 8 2 Periodic...

Страница 28: ...ndstill While keeping STO IN1 energized de energize the STO IN2 circuit and give a start command for the drive Ensure that the motor remains at a standstill Energize the STO IN2 circuit Restart the dr...

Страница 29: ...tion An internal power source in the drive is brought out to the Safety connector J4 Connecting the STO inputs between this bypass power source and its ground supplies power to the STO opto couplers a...

Страница 30: ...ve service Evaluate the impact of decommissioning on adjacent operating units and facilities or other field services Conduct a proper review and obtain required authorization Ensure that the safety fu...

Страница 31: ...Manual 16 01553 Rev 00 Page 31 of 31 Copley Controls Xenus Plus Compact STO Manual P N 16 01553 Revision 00 September 12 2016 2016 Copley Controls Analogic Motion Controls 20 Dan Road Canton MA 02021...