Fan On/Off setting
Parameter
Fan on
Fan off
Load
>500W
<200W
Extrusion temp
>60C
<55C
Rectifier Diode
>70C
<60C
Display Panel Indicators / Switches
‐ ‘Main’ On/Off momentary switch
‐ ‘Select’ momentary switch
‐ 3 x 7‐segment LED display
‐ ‘STATUS’ LED (tri color)
‐ ‘Battery Voltage’ LED (Green)
‐ ‘Battery Current’ LED (Green)
‐ ‘Output Power’ LED (Green)
‐ Remote communication cable, 6‐wire, 25ft long (P/N 31‐5267‐00)
User Messages / Diagnostics
The following Fault codes are provided on digital display when system Fault/Warning occurs:
E01: DC Input Under‐Voltage Shutdown
E02: DC Input Over‐Voltage Shutdown
E03: Inverter Output Overload (or Short Circuit) Shutdown
E04: Inverter Over‐Temperature Shutdown
E05: DC Input Under‐Voltage Warning
E06: Inverter Output Overload Warning
E07: Inverter Over‐Temperature Warning
E08: Not used
E09: Not used
E10: Charger Output Over Voltage Shutdown
E11: Battery not accepting charge
E12: Transfer Relay Over‐Temperature Shutdown