40
Charger and AC Transfer Section
AC Input Surge Protection
‐ 175 J MOV is connected across the Line and Neutral of AC Input
Charger DC Output Over Voltage Shutdown
‐ Battery Over voltage protection: 16.0 +/‐ 0.5Vdc (Error code: E10)
‐ Audio Alarm: Beep @ 1 Hz and AC charger is latched off
‐ Bypass mode is available
‐ To reset error code, remove AC Input and turn unit off and on
Dead
Battery
Charging
Battery voltage must meet the following conditions or Error code E11 will display:
‐ Initial battery voltage must be 10V or higher for charge to commence
‐ In event battery voltage drops below 10V after charge is initiated (Added Load)
Maximum time for battery voltage to rise above 10V in Bulk charge: 15 minutes
‐ Audio Alarm: Beep @ 1 Hz and AC charger is latched off following 15 minute delay
‐ Bypass mode is available
‐ To reset error code, remove AC Input and cycle unit off and on until reset
Parametric Display
The two buttons on the display panel can be used to select what is being displayed on the
screen and to enter into feature select mode. To select what is being displayed on the
screen during inverter mode, press ‘Select’ button to toggle the display to show following:
‐ DC Input Voltage in Vdc with ‘Input Voltage’ LED On
‐ AC Output Power in kW with Output Power’ LED On
‐ Inverter function setting ‘In0/1’ with Input Voltage and Output Power LED Off
‐ Charger current setting in Adc with Input Voltage and Output Power LED Off
‐ Alarm function setting ‘AL0/1’ with Input Voltage and Output Power LED Off
‐ Under voltage shutdown setting ‘sdL/n/h’ with Input Voltage and Output Power LED
Off
‐ Battery Type [FI]=Fixed, ‘FLo’=Flooded, ‘gEL’=Gel, ‘Ag’=AGM