37
AC
Output
Overload
Protection
and
Warning
and
Shutdown
Model
Condition
Power (W)
Dis‐
play
Audible alarm
V<11.4
11.4<V<11.8
V>11.8
12‐110‐1000‐xx
Warning (+/‐100W)
950
1000
1100
E06
Beep @ 0.33Hz
Shutdown (+/‐100W)
1050
1100
1200
E03
Beep @ 1 Hz
12‐110‐1800‐xx
Warning (+/‐200W)
1750
1850
2000
E06
Beep @ 0.33Hz
Shutdown (+/‐200W)
1850
1950
2100
E03
Beep @ 1 Hz
AC Output Short Circuit Protection
A short circuit may be applied to the AC output continuously during inverter mode without damage
to any components. Unit will shut down within 10 seconds, and display will indicate ‘E03’ with the
buzzer beeping @ 1 Hz.
Note:
Manual reset is required to restart Inverter after AC Overload or Short Circuit shutdown.
System will automatically reset AC Overload or Short Circuit shutdown error when utility is
available. The supplemental protector or the branch protection specified in the Installation Guide
should be open under bypass short circuit output condition.
Incorrect Connection Protection
Inverter DC Input Protection
AC Input and AC Output:
AC Input Line and Neutral reverse connection cannot be detected. Input and output
ac terminals are labeled, and unit is installed by a professional installer.
Charger DC Output Protection:
Reverse polarity on DC terminal will blow the charger DC input fuses. This damage
is not covered under warranty.