1
st
Issue 09/05 8
DMP026E
Addressing
The default address for a standalone DG500 Controller is “Subnet 1 Node 2”, i.e. switch 2 set
to ON.
Each DG500 Controller has a unique address for communicating with a PC or modem.
a) Ensure the controller is not powered up.
b) Set switches 1 to 7 to the appropriate ON/OFF position to enable the binary address.
c) Power up the controller.
Example: to configure address 37: set switches 1, 3 and 6 to ON and the other switches to
OFF position.
Wiring
The following electrical connections can be made to DG500 controllers:
•
NCP connection to a MicroNet NCP Interface (MNN-MI-100) and other NCP type
DG50XX controllers
•
I/O connections, including:
•
Ten configurable Universal Inputs (UIs)
•
Two digital inputs
•
Six digital outputs (Line Relay)
•
Four analogue outputs (0 to 10V)
•
24 Vac nominal EN 60742 power source and earth ground power connection.