Resistive (NTC temperature sensors) Input
1. Review Precautions section.
2. Connect one wire from sensor or resistive device to desired input terminal. Polarity is not
important.
3. Connect other wire to one common (0V) terminal.
4. Make certain input configuration jumper is in Resistive position (Link A).
Digital inputs
Note: Only dry (voltage free) contacts can be monitored. Maximum count frequency is once
every two seconds.
1. Review Precautions section.
2. Connect one wire from field contact to desired input terminal. Polarity is not important.
3. Connect other wire to one common (0V) terminal.
4. Make certain input configuration jumper is in Digital position (Link B).
Digital Outputs (DO)
Note: Each load must be externally powered.
Relay outputs must control single-phase loads (only 24Vac or 230 Vac –110 VA)
otherwise, use external relays.
DOs 1 through 6 are Form A (N.O.) relay outputs for switching up to 230Vac, 5A loads only.
1. Review Precautions section.