Issue 09/05 30
DMP026E
Test? 52
If it is set to On, it overrides the valve outlet at 100%, disabling the coil control. Set it back to
Off at the end of the test phase.
Cooling Loop
Select this menu for menu to display and/or edit the data related to the fan coil cold fluid
distribution.
Opening 53
It displays the valve opening percentage (read-only).
P. Band. 54
It displays the loop proportional band (read/write). Default value: 15.
I Time 55
It displays the loop integral time (read/write). Default value: 90.
Test? 56
If it is set to On, it overrides the valve outlet at 100%, disabling the coil control. Set it back to
Off at the end of the test phase.
Pump FC1 57
It displays the digital output status of the 2-pipe fan coil pump or of hot fluid distribution in
four-pipe fan coil.
Pump FC2 58
It displays the digital output status of cold fluid distribution in four-pipe fan coil. Do not use in
two-pipe fan coil.
FanCoil Schedule 59
On
Off
On
Off
Monday
00:00
23:59
23:59
23:59
Tuesday
00:00
23:59
23:59
23:59
Wednesday
00:00
23:59
23:59
23:59
Thursday
00:00
23:59
23:59
23:59
Friday
00:00
23:59
23:59
23:59
Saturday
00:00
23:59
23:59
23:59
Sunday
00:00
23:59
23:59
23:59
See the paragraph “Start-up” to customise time schedule.
S/W C.O. 60
Outside summer/winter switch. On = Summer. If it is present and On, the On/Off humidifier is
disabled, and the two-pipe fan coil uses the cooling loop.