1
st
Issue 09/05 29
DMP026E
Heat SP 44
Actual operating set point for heating loop (read-only).
Cool T. 45
It displays the cold fluid temperature. Read-only.
Fixed SP 46
Value of the fixed (editable) SP for cold fluid temperature; it is on only if the outside sensor is
not connected. Default value 9°C.
Cool Comp. 47
Compensation curve for cold fluid temperature.
outside t.
Cold SP
20
12
25
9
It is possible to edit and/or add values to the curve. In case it is necessary to delete already
existing value pairs, just set a room t. value equal to the preceding one in the table.
Example:
outside t.
Cold SP
20
12
25
9
40
8
outside t.
Cold SP
20
23
25
9
40
9
Cool SP 48
Actual operating set point for cooling loop (read-only).
Note. In case of 2-pipe fan coil, T. Hot and T. Cold will display the same value.
Heating Loop
Select this menu for menu to display and/or edit the data related to the fan coil hot fluid
distribution.
Opening 49
It displays the valve opening percentage (read-only).
B. Band. 50
It displays the loop proportional band (read/write). Default value: 15.
I Time 51
It displays the loop integral time (read/write). Default value: 90.
25
20
9
12