LCD DISPLAY
It allows displaying and/or editing the controller parameters, inputs and outputs.
Menu Options Description
NOTE: The default proportional band of the loop is = 15K. In case the loop controls on
a room or return sensor, it is advisable to edit the proportional band = 2K.
Out Temp 1
It displays outside temperature. Its presence enables compensation on each control loop. If it
is not present, fixed control is carried out on each loop (see the relevant submenu).
AHU schedule 2
On
Off
On
Off
Monday
00:00
23:59
23:59
23:59
Tuesday
00:00
23:59
23:59
23:59
Wednesday
00:00
23:59
23:59
23:59
Thursday
00:00
23:59
23:59
23:59
Friday
00:00
23:59
23:59
23:59
Saturday
00:00
23:59
23:59
23:59
Sunday
00:00
23:59
23:59
23:59
See the paragraph Start-up in order to customise time schedules.
Press. Swh 3
It displays the pressure switch status. On = dirty filter.
Hum. Swh 4
It displays the humidity switch status. On = humidity < setpoint
Dmp_Stat 5
It displays the status of the stroke end micro switch. On = open damper.
Frost P. 6
It displays the antifrost alarm status. On = antifrost alarm.