28
Unidrive M200/201 Control Quick Start Guide
Issue Number: 3
The table below gives all the possible analog input modes.
Pr
17
determines whether the reference is uni-polar or bi-polar. See
Minimum Speed
(Pr
01
). Allows
negative speed reference in keypad mode.
If the preset reference has been selected (see Pr
05
), the speed at which the motor runs is
determined by these parameters. See
Drive Configuration
(Pr
05
).
Value
Text
Function
-6
4-20.S
Stop on loss
-5
20-4.S
Stop on loss
-4
4-20.L
4-20 mA switching to equivalent of 4 mA input current on loss
-3
20-4.L
20-4 mA switching to equivalent of 20 mA input current on loss
-2
4-20.H
4-20 mA hold at level before loss on loss
-1
20-4.H
20-4 mA hold at level before loss on loss
0
0-20
0-20 mA
1
20-0
20-0 mA
2
4-20.tr
4-20 mA trip on loss
3
20-4.tr
20-4 mA trip on loss
4
4-20
4-20 mA no action on loss
5
20-4
20-4 mA no action on loss
6
Volt
Voltage
In 4-20 mA and 20-4 mA modes loss of input is detected if the current falls below 3 mA.
If both analog inputs (A1 and A2) are to be set-up as voltage inputs, and if the
potentiometers are supplied from the drive's +10 V rail (terminal T4), they must have a
resistance >4 k
Ω
each.
17
Bipolar Reference Enable
RW
Bit
US
OL
Ú
Off (0) or On (1)
Ö
Off (0)
RFC-A
18 to 21
Preset Reference 1 to 4
RW
Num
US
OL
Ú
0.00 to Pr
02
Hz
Ö
0.00 Hz
RFC-A
NOTE
NOTE