1. Before Using the Product
6
ADI16-4(FIT)GY
Handling Precautions
Take the following precautions when handling this module.
-
Do not modify the module. CONTEC will bear no responsibility for any problems, etc., resulting
from modifying this module.
-
Do not use or store the equipment in a hot or cold place, or in a place that is subject to severe
temperature changes. (Operating temperature range: 0 to 50
°
C)
-
Do not use or store the equipment in a place subject to direct sunlight or near a heating device,
such as a stove.
-
Do not use or store the equipment in a dusty or humid place. (Operating humidity range: 10 to
90%, no condensation)
-
As this product contains precision electronic components, do not use or store in environments
subject to shock or vibration.
-
Do not use or store the product near equipment generating a strong magnetic field or radio waves.
-
If you notice any strange odor or overheating, please unplug the power cord immediately.
-
In the event of an abnormal condition or malfunction, please consult the dealer from whom the
equipment was purchased.
-
To avoid electric shock, please do not touch the system with a wet hand.
-
Do not open the module casing. CONTEC will disclaim any responsibility for equipment whose
casing has been opened.
-
To prevent damage, please do not subject the module to impact or bend it.
-
To prevent contact malfunction, please do not touch the metallic pins on the external module
connector.
-
The module contains switches that need to be properly set. Before using the module, please check
its switch settings.
-
To avoid malfunction, please do not change the module switch settings in an unauthorized
manner.
-
"Do not operate the device module when the power for the Controller Module is on.
To avoid malfunction, please be sure to turn off the power for the Controller Module."
-
If you use this product in a noisy environment, attach ferrite cores to the IO cable to stabilize the
operation.
-
Regarding “FCC PART 15 Class A Notice”
This product has acquired the above-mentioned standard.
However, a sufficient margin may not be secured for the standard. In this case, use a ferrite core
(SEIWA E04SR200917 or a compatible product) for the interface cable or the power cable of the
controller unit to which a ferrite core (SEIWA E04SR301334 or a compatible product) is
connected.
When attaching a ferrite core to the interface cable, just put the cable inside the case; when
attaching a ferrite core to the connecting power cable of the controller unit, coil it around once
near the connector while leaving it open, and then close it.
CAUTION