Safe-Lec 2 Conductor Bar Manual
29
Collector Base Material
Torque Spec
Aluminum
24.4 to 27.1 Nm (18-20 ft-lb)
SECTION 16 - 200 AMP COLLECTOR MOUNTING DETAILS
NOTE
• Torque mounting hardware per the chart below.
• In a stationary position, these collectors are UL rated at 100 amps continuous-duty on copper, and 50 amps on aluminum-
stainless steel.
Figure 29-1
XA-SL2C-200S-1M
Contact Surface
Working Range
2.75
(69.9)
1.25
(31.8)
4.0
(102)
2
1
4.0
(102.0)
Contact Surface
Working Range
2.75
(69.9)
1.25
(31.8)
Figure 29-2
XA-SL2C-200T-1M
P/N XA-590062 Ground Flag
Installation
1. The ground flag should be oriented on the ground collector with the flag facing
away from the other phase collectors as to prevent the ground conductor from
being inserted into any of the phase rails.
2. Align the two 3.2mm through holes located near the pivot post on the head with
the two holes on the ground flag.
3. The supplied M3 locking nuts should be inserted into the flag where the
hexagonal nut bosses are molded into the flag. Orient the nylon section of the
nuts facing away from the collector.
4. Insert the two M3 x 30 screws through the collector head and into the flag and
flag nuts.
5. Tighten the M3 screws to 0.9N-m (8in-lb)
NOTE:
Cable length between the exit of
the cable clamp and the cable
entry hole on the collector head
should be 18” for 100 Amp Col-
lectors and 19.5” for 200 Amp
Collectors to ensure proper head
movement on the collectors.