Safe-Lec 2 Conductor Bar Manual
SECTION 2 - GENERAL INSTALLATION INSTRUCTIONS
Phase 5 Collector Positioning
Properly position and align Collector Assemblies to ensure safe, reliable operation.
• For 100A and 200A collectors, the center line of the collector mounting post must be 102mm (4.0”) below the contact surface of the
conductor bars. When installed, the collector arms should be parallel with the contact surface of the bar.
• Slide the collectors on the mounting staff. Ensure the mounting base of each collector is centered below the corresponding conductor.
Ensure the collectors are evenly spaced. Tighten hardware to specifications and connect the supply cable to the collector per diagram
(see Table of Contents).
NOTES
• Follow lockout-tagout procedures.
• Keep accessories at least 6” from hanger brackets.
• Follow all torque specifications.
• Allow for movement of accessories due to expansion.
• Connect only flexible power cables to powerfeed assemblies.
• Keep collectors straight, level and aligned with conductors.