9
Product Overview
3
Product Overview
3.1
Models overview
Condair RS steam humidifiers are available as
single units with different housing sizes (S, M and
L)
, as
double units (2 x "M")
and as
Linkup systems
(3 x "M" or 4 x "M")
with
different heating
voltages
and
steam capacities ranging from 5 kg/h up to a maximum of 160 kg/h
.
3.1.1 Single units Small ("S") , RS 5...10 and Medium ("M"), RS 16...40
Housing
size
Condair
230 V/1~ 200V/3~ 230V/3~ 380V/3~ 400V/3~ 415V/3~ 440V/3~ 460V/3~ 480V/3~ 500V/3~ 600V/3~
kg/h
kg/h
kg/h
kg/h
kg/h
kg/h
kg/h
kg/h
kg/h
kg/h
kg/h
S
RS 5
5.0
––
5.0
4.6
5.0
5.4
––
––
––
––
––
RS 8
8.0
––
8.0
7.3
8.0
8.7
––
––
––
––
––
RS 10
9.8
––
9.8
9.0
10.0
10.7
10.8
11.8
12.8
13.9
10.3
M
RS 16
––
14.9
16.0
14.5
16.0
17.3
15.3
16.7
18.2
19.8
14.2
RS 20
––
18.1
19.7
17.9
20.0
21.4
17.2
18.8
20.5
22.2
21.3
RS 24
––
22.3
24.0
21.8
24.0
26.0
––
––
––
––
––
RS 30
––
30.0
29.5
26.9
30.0
32.0
24.0
26.2
28.6
31.0
32.0
RS 40
––
––
––
36.1
40.0
43.1
36.0
39.4
42.9
46.5
42.7
Fig. 1: Overview single units Small ("S") and Medium ("M")
I/O
Driver board
Module A
Control
board
RFI
Heating voltage
Module A
Control voltage
Control signal
External enable
Limiter signal
Safety chain
Remote indication
Main
Module A
Содержание RS series