5.6.3 System 3 – Supply air humidity control with continuous output limit ation
Supply air humidity control (humidity sensor installed in supply air duct) should be used only
where room humidity control is impracticable for technical reasons
. Such systems always require
a PI-controller.
The humidity sensor (A1) is located in the supply air duct after the steam distribution pipe. The humidity
sensor (A2) for the continuous output limitation is located in the supply air duct before the steam distri-
bution pipe. Such a system requires a PI-controller with the option to connect a second humidity sensor.
Fig. 26: System 3 – Supply air humidity control with continuous output limit ation
5.6.4 Which humidity control system for which application
Application
Location of the humidity sensor
room or exhaust air duct
supply air duct
Air conditioning systems with:
– supply air portion up to 33%
System 1
System 1
– supply air portion up to 66%
System 1 or 2
System 2 or 3
– supply air portion up to 100%
System 2
System 3
– supply air humidity control
—
System 3
Direct room humidification
System 1
—
Please contact your Condair supplier, if your application meets the following conditions:
– Humidification of small rooms up to 200 m
3
– Air conditioning systems with a high number of air exchanges
– Systems with variable air volume flow
– Test facilities with extreme control accuracy requirements
– Rooms with a high variation in max. steam capacity
– Systems with temperature fluctuations
– Cold rooms and systems with dehumidification
A1/2
humidity sensor
B1
ventilation interlock
B2
airflow monitor
B3
safety humidistat
PI
I
Internal PI controller
PI
E
External PI controller
Y
input signal from A1
Z
input signal from A2