Product Overview
3.4.2 Accessory details
3.4.2.1 DV81-... steam distribution pipe
The steam distribution pipes are selected on the basis of the
duct width "B"
(for horizontal installation)
or the
duct height "H"
(for vertical installation) and the
capacity of the steam humidifier
.
Important!
Always select the longest possible steam distribution pipe (opti mum humidification distance).
Steam distribution pipe DV81-... made of CrNi steel Duct width/duct height
Max. Steam capacity
Type
Length in mm (L) ***
in mm
in kg/h
DV81-200 *
200
210...400
10
DV81-350 **
350
400...600
30
DV81-500 **
500
600...750
30
DV81-650
650
750...900
50
DV81-800
800
900...1100
50
DV81-1000
1000
1100...1300
50
DV81-1200
1200
1300...1600
50
DV81-1500
1500
1600...2000
50
DV81-1800
1800
2000...2400
50
DV81-2000
2000
2200...2600
50
DV81-2300
2300
2500...2900
50
DV81-2500
2500
2700...3100
50
* for units with steam capacities up to a maximum of 10 kg/h only
** for units with steam capacities up to a maximum of 30 kg/h only
*** Special length on request
Note: for further information regarding the DV81-... steam distribution pipe please refer to the separate
installation and operating instructions of this product.