59
Mounting and installation work
5.7.3 Wiring diagram Condair RS 50...80 - Single units "L"
Fig. 28: Wiring diagram Condair RS - Single units "L" 50...80 kg/h
H1
Error
1 2 3
Service
4 5 6
Steam
7 8
Unit On
9 10
H2
Hyg. Valve A
FAN B
1 2 3
Hyg. Valve B
4 5 6 7 8
FAN A
9 10
MAINS SUPPLY
L N SC1SC2PEPE
MODULE B
24VDC
LEVEL
UNIT
POWER
BOARD
DRN1 J2 INLET J1
PWR
SUPPLY
BLOWER
LIMIT
ENABLE
CONTROL
V+
X8
X9
X12
X11
X10
X7
X1
INGND IN GND
24V IN
24V IN
24V GND
RS485
RS485
PWRIC
CONT-
ACTOR
HEAT GR.
2+3
JP2 (24V)
JP1 (10V)
PUMP
AC
SWITCH
GND
D–
D+
GND
D–
D+
24V
GND
DRN2 J3
F1
SW1
F2
MAINS SUPPLY
L N SC1SC2PEPE
MODULE B
24VDC
LEVEL
UNIT
POWER
BOARD
DRN1 J2 INLET J1
PWR
SUPPLY
BLOWER
LIMIT
ENABLE
CONTROL
V+
X8
X9
X12
X11
X10
X7
X1
INGND IN GND
24V IN
24V IN
24V GND
RS485
RS485
PWRIC
CONT-
ACTOR
HEAT GR.
2+3
JP2 (24V)
JP1 (10V)
PUMP
AC
SWITCH
GND
D–
D+
GND
D–
D+
24V
GND
DRN2 J3
F1
SW1
F2
ACCESSORY BOARD
REMOTE BOARD
BMS
LinkUp
SAB
3V
CR2032
BAT
SD
J7
J4
J8
J11
(USB)
(RJ45)
GND
+
–
GND
+
–
GND
+
–
24V
GND
L1 L2 L3
L1 L2 L3
K1
L1 L2 L3
L1
L2
L3 PE
Q3
F3
400-415 V/3~/50..60 Hz
B3
K2
B2
B1
L1 N PE
F4
Q4
230 V/1~/50..60 Hz
J3
230V
140Ω...10kΩ
A2
On/Off
A3
GND
IN
V+
IN
V+
JP1
JP2
A1
A4
Y
+ –
Z
+ –
B4
140Ω...10kΩ
A5
GND
IN
V+
JP1
Z
Y1
Y1
J1
J1
J3
Control compartment
Module A
Module B
Control board
Driver board Module B
Driver board Module A
A1 Continuous humidity controller (active) or humidity sensor
A2 Ohmic humidity controller (passive), set jumper JP1 and remove jumper JP2
A3 On/Off humidity controller, set jumper JP2 and remove jumper JP1
A4 Limiter signal
A2 Ohmic limiter controller, set jumper JP1 and remove jumper JP2
B1 Ventilation interlock
B2 Airflow monitor
B3 Safety humidistat
B4 External enable contact
F1
Internal fuse 24V supply (1 A, slow acting)
F2
Internal fuse 230V supply (6.3 A, slow acting)
F3
External fuse heating voltage supply (see table in
chapter 5.7.7
)
F4
External fuse control voltage (max. 10 A, slow acting)
J1
Jumper wire, if blower pack safety loop is not connected
J3
Jumper wire, if no monitoring devices are connected to SC1 and SC2
J4
Jumper for activating the terminating resistor for Modbus network (Jumper must be connected, if Condair RS
is the last unit in the Modbus network)
J7
Jumper for activating Modbus or BACnet MSTP communication via RS485 interface (J6). If jumper is not in
place no communication will take place through the RS485 interface.
H1 Remote operating and fault indication (option)
H2 Accessory board (option) for the control of an external fan of the AHU as well as the optional external valve for
the water supply line flushing
K1 Mains contactor (heating voltage) module A / module B
K2 External safety circuit (safety humidistat, airflow monitor, etc.)
Q3 External main switch heating voltage supply
Q4 External main switch control voltage supply
SW1 Rotary switch Module identification (Module A: 0, Module B: 1)
Y1 Total drain valve (option)
Ethernet (RJ45) IP
network / BMS BACnet IP
RS 485 BACnet MSTP