59
Fault elimination
8.2
Fault indication on the Condair RH
blinks blue
Safety loop open (W2)
lights red
No WiFi connection (W6)
lights yellow
End of service life of steam cylinder soon reached (W5)
lights red
lights red
End of service life of steam cylinder reached (E5)
Wrong steam cylinder installed (E6)
lights
yellow
1)
Connection to the humidity sensor interrupted (W3)
Connection to the limiter sensor interrupted (W4)
Timeout for receiving a WiFi signal reached (W6)
lights
red
1)
Overcurrent detected (E1)
Problem detected with inlet and outlet (E2)
No current even though there is a demand for humidity (E3)
Fault in driver board (E4)
1)
The malfunction code can only be queried via the HumiLife app.
8.3
Fault indication in the HumiLife app
If a malfunction occurs, the yellow warning triangle appears on the home screen of the HumiLife app. If
you tap on it, a window appears with the error message (warning or error), the error code and informa-
tion on how to remedy the malfunction.