Thank you for choosing Condair

Installation date (MM/DD/YYYY):

Commissioning date (MM/DD/YYYY):

Site:

Model:

Serial number:

Proprietary Notice

This document and the information disclosed herein are proprietary data of Condair Group AG. Neither this docu-

ment, nor the information contained herein shall be reproduced, used, or disclosed to others without the written 

authorisation of Condair Group AG, except to the extent required for installation or service of recipient's equipment.

Liability Notice

Condair Group AG does not accept any liability due to incorrect installation or operation of the equipment or due 

to the use of parts/components/equipment that are not authorised by Condair Group AG.

Copyright Notice

© Condair Group AG, All rights reserved.

Technical modifications reserved

Содержание RH 1.8

Страница 1: ...Humidification and Evaporative Cooling 2600951 B EN 2104 INSTALLATION AND OPERATION MANUAL Steam humidifier Condair RH...

Страница 2: ...hall be reproduced used or disclosed to others without the written authorisation of Condair Group AG except to the extent required for installation or service of recipient s equipment Liability Notice...

Страница 3: ...instructions for installation work 18 5 2 Placement and installation of the steam humidifier 19 5 2 1 Placement of the steam humidifier 19 5 2 2 Mounting the steam humidifier 22 5 3 Water installation...

Страница 4: ...ment of the steam cylinder 49 7 4 1 1 Removal of the steam cylinder 49 7 4 1 2 Installation of the steam cylinder 50 7 4 2 Removal and installation of the components of the Condair RH for maintenance...

Страница 5: ...will be glad to assist you 1 2 Notes on the installation and operation manual Limitation The subject of this installation and operation manual is the Condair RH steam humidifier in its different vers...

Страница 6: ...word DANGER used in conjunction with the general caution symbol designates safety and danger notes in this installation and operation manual that if neglected may lead to severe injury or even death o...

Страница 7: ...m humidification system are familiar and comply with the appropriate regulations on work safety and the prevention of accidents The Condair RH can be used by children aged 8 years and over and by pers...

Страница 8: ...y out any work on the steam humidification system during operation steam lines steam distribution unit etc If the steam humidification system is leaky set the Condair RH im mediately out of operation...

Страница 9: ...owner without delay to shut down the Condair RH and to secure it against accidental power up Prohibited modifications to the unit NomodificationsmustbeundertakenontheCondairRHwithouttheexpresswrittenc...

Страница 10: ...ipt of the goods Condair Group AG assumes no responsibility for any material shortages beyond this period Unpack the parts components and check for any damage If parts components are damaged notify th...

Страница 11: ...specification label for the location of the specification label see unit overview Condair Ltd 2740 Fenton Road Ottawa Ontario K1T3T7 Canada Type RH EU 1 8kg h Serial No XXXXXXX 04 2020 Heating voltage...

Страница 12: ...6 Water fill hose 7 Steam cylinder sealing 8 Steam cylinder 9 Drain pan 10 Water inlet valve 11 Drain valve 12 Cable feedthrough 13 LED s operating status 14 Specification label 15 On Off switch 16 D...

Страница 13: ...y the inlet valve closes If the steam generation decreases below a certain percentage of the required capacity due to lowering of the water level e g because of the evaporation process or drainage the...

Страница 14: ...cm Drain hose innner diameter 22 mm Open funnel with trap by others Ventilation unit HRV Mains socket 230 V 1 50 60 Hz by others Mains cable RH 1 8 only 1 Insulation hose EcoTherm Air flow monitor ext...

Страница 15: ...e DS22 Insulation hose EcoTherm Mains socket 230 V 1 50 60 Hz by others Mains cable RH 1 8 only 1 Condensate hose KS10 8 12 mm Insulation slotted fabric hose Filter valve accessory Z261 or Shutoff val...

Страница 16: ...hers Mains socket 230 V 1 50 60 Hz by others Mains cable RH 1 8 only 1 Condensate hose KS10 8 12 mm Air flow monitor optional external safety loop Insulation slotted fabric hose Filter valve accessory...

Страница 17: ...1 8 RH 3 6 Filter valve 1x Z261 Accessory steam installation Condair RH RH 1 8 RH 3 6 Steam hose DS22 Insulation hose for steam hose EcoTherm Condensate hose KS10 Insulation hose for condensate hose S...

Страница 18: ...and electrical installations Safety For some of the installation work the device covers of the Condair RH must be removed Therefore make sure to observe the following safety notes DANGER Danger of el...

Страница 19: ...and weights 265 mm 500 mm 200mm 200mm 600 mm 467 mm 175 mm recommended minimum clearances Note For the installation of the steam humidifier between the pipes of the HRV ventilation unit there must be...

Страница 20: ...t as possible max 4 m the minimum bend radius Rmin 250 mm and the minimum upslope and downslope of 10 of the steam hose from the steam humidifier to the steam distribution unit are maintained The stea...

Страница 21: ...r in such a manner that it is freely accessible with sufficient space available for maintenance purposes The minimum distances shown in Fig 5 should be observed if possible Make sure that the steam hu...

Страница 22: ...up 1c Lift the steam cylinder at an angle upwards out of the humidifier 1a 1b 1c 2 1 Mount the steam humidifier on the wall 2 1a Mark the fixing points A and B at the desired location on the wall usin...

Страница 23: ...e of 5 mm between the screw head and the wall 2 1d Hang the unit onto the previously installed screw 2 1c 2 1d 5 mm A A A A 2 1e Screw a screw through the rear wall of the unit into the fixing hole B...

Страница 24: ...insert dowels 2 1c 2 1d 75 mm C C 2 2c Fasten the ceiling bracket with two screws 2 2d Fasten the unit to the ceiling bracket through the rear wall of the unit with M6 screws Then align the unit with...

Страница 25: ...Installation 3 Install the steam cylinder 3a Insert the steam cylinder into the receptacle in the unit at an angle from above 3b Push the lever down as far as it will go 3c Close the unit door 3a 3b...

Страница 26: ...ilter 125 m Water supply hose PEX armored hose G 3 4 G 3 4 supplied 2 6 bar 4 30 C 125 1250 S cm Drain hose 20 26 mm supplied min downslope 15 8 5 to the funnel Drain connection 20 mm Water supply con...

Страница 27: ...ng water regulations with a con ductivity of 125 1250 S cm to feed the steam humidifier The use of reverse osmosis water or deionized water is not permitted The use of additives such as corrosion inhi...

Страница 28: ...via appropriate cable strain relief or grommets The cable for the heating voltage supply must be lead into the unit from the bottom via the cable opening equipped with the clamp Fix the cable with the...

Страница 29: ...oor 1b undo the two screws on the control compartment cover and remove it 1a 1b 2 Make electrical connections according to Section 5 5 3 3 Close the front covers 1a Attach the control compartment cove...

Страница 30: ...NO 0V 24V DO1 DO1 1 2 3 4 24V AC DC 0V GND H OUT 1 2 3 brown green green green white yellow yellow white yellow brown Driver board brown Condair RH Fig 8 Wiring diagram Condair RH Legend A1 Humidity...

Страница 31: ...d the optionalAir flow monitor B2 are connected to the corresponding terminals of the terminal blocks X3 X4 and X5 on the driver board of the Condair RH according to the diagram Note If no air flow mo...

Страница 32: ...The humidity sensor B1 is connected to the corresponding terminals of the terminal block X2 on the driver board of the Condair RH according to the wiring diagram Note The wiring diagram shows the conn...

Страница 33: ...by others in the mains supply line are mandatory For safety reasons the additional installation of a residual current circuit breaker in the mains supply line supplied by others is recommended However...

Страница 34: ...supply pipe maintained throughout the entire length Is the steam humidifier connected to a tap water network and is the conductivity of the supply water between 125 1250 S cm Are all components and pi...

Страница 35: ...ng to the corresponding wiring diagram Are all connection cables correctly attached Are the connection cables strain relieved passed through the cable gland Have the local regulations for the executio...

Страница 36: ...ng in the specified order Inspecting the steam humidifier for correct installation Inspecting the electrical installation Inspecting the water installation Inspecting the steam installation Flushing t...

Страница 37: ...ir RH was switched off via the HumiLife app The Condair RH does not humidify again until it is switched on via the HumiLife app LED blinks blue Safety loop open W2 LED lights red The Condair RH is swi...

Страница 38: ...ly be operated by persons who are familiar with the Condair RH and who are sufficiently qualified for this work The following describes the procedure for commissioning the Condair RH after an interrup...

Страница 39: ...1 Inspections during operation The hygiene regulations of Standard VDI 6022 stipulate that during operation the operator regularly checks the condition of the humidifier and the components of the hum...

Страница 40: ...at least 20 minutes 3 If maintenance work is to be carried out on the Condair RH or the steam humidification system Close the filter valve or the shut off valve in the water supply line Disconnect the...

Страница 41: ...mobile phone 6 6 2 Connect the HumiLife app to the Condair RH 1 Go to Settings on your mobile phone and activate the WLAN function 2 Open the HumiLife app The login screen appears If you do not have a...

Страница 42: ...have yet been registered under your user account press Add Device left screen otherwise press Add new device right screen 4 Press the device switch on the humidifier approx 5 seconds until the WiFi sy...

Страница 43: ...Then select the Condair RH from the list of WLAN devices and return to the HumiLife app figure in the middle Press Continue in the HumiLife app screen figure on the far left The HumiLife app confirms...

Страница 44: ...nd confirm it with Save and connect The HumiLife app confirms that the network configuration has been successfully completed Press Continue to confirmation The HumiLife app connects to the cloud Once...

Страница 45: ...ng the home screen this screen 9 Accessing the User Settings Menu Measured value graph and maintenance information Press the graphic symbol 4 on the home screen The measured value graphic appears figu...

Страница 46: ...and conditions Under my devices Add a new device to your account Select a device from the list of devices in your account and then view the current device data change the device name change the sensor...

Страница 47: ...ation Prevention Before carrying out any maintenance work set the Condair RH out of operation as de scribed in Section 6 5 switch off the unit disconnect it from the mains and stop the water supply an...

Страница 48: ...al maintenance of the Condair RH steam humidifier Components Work to be done Steam cylinder Replace as soon as the cylinder status LED and the fault LED light up yellow Drain valve Remove disassemble...

Страница 49: ...f operation in accordance with Section 6 5 and secured against unintentional restart 7 4 1 Replacement of the steam cylinder 7 4 1 1 Removal of the steam cylinder 1 Open the unit door 2 Pull the lever...

Страница 50: ...a the On Off switch on the unit Note The control of the Condair RH automatically recognizes that a new steam cylinder has been inserted and automatically resets the maintenance counter Note If the fau...

Страница 51: ...e the cover 3 Use a flat blade screwdriver to press in the two tabs that secure the cover of the internal water system to the housing of the Condair RH One tab is on the top and one is on the separati...

Страница 52: ...nect the plug connection of the connection cable on the drain valve 2 Disconnect the hose from the connector on the drain valve 1 2 Fig 10 Unplug the connection cable and pull off the hose 3 Push the...

Страница 53: ...otective disk 6 Disconnect the solenoid from the drain valve Then remove the valve stem and spring 6 Fig 13 Disassemble the drain valve The assembly and installation of the drain valve is carried out...

Страница 54: ...the inlet valve Note The polarity of the electrical cables does not have to be observed 2 Loosen the hose clamp and pull the hose off the connector 3 Loosen the water supply hose and remove the hose...

Страница 55: ...e hoses connected to the fill cup can also be removed together with the fill cup and only removed from the connections on the fill cup afterwards 2 Press the snap lock on the rear wall backwards a and...

Страница 56: ...re brush Thoroughly rinse the drain valve and the valve stem with fresh tap water Let the drain valve dry before reinstallation Fill cup Carefully remove any limescale from the fill cup and its connec...

Страница 57: ...ouch with the acid and its vapours wear goggles and work in a well ventilated room or outside CAUTION Do not use soap to clean the parts since residual soap can cause foaming which will affect proper...

Страница 58: ...Safety Before starting repair work on the Condair RH set the unit out of operation and disconnect it from the mains see Section 6 5 DANGER Make sure the Condair RH is separated from the mains check wi...

Страница 59: ...limiter sensor interrupted W4 Timeout for receiving a WiFi signal reached W6 lights red 1 Overcurrent detected E1 Problem detected with inlet and outlet E2 No current even though there is a demand for...

Страница 60: ...re is no system error and the unit is switched on again via the HumiLife app Ventilation switched off Check switch on ventilation Maximum humidistat or air flow monitor has responded Check the setting...

Страница 61: ...ean or replace the drain valve E3 lights red E3 No heating current detected No heating current was measured for 20 minutes although there is a humidity demand present The Condair RH is stopped Electri...

Страница 62: ...App Possible causes Remedy E6 lights red lights red E6 Invalid cylinder installed Cylinder not installed correctly contact cylinder fuse bad Install cylinder correctly The controller cannot verify th...

Страница 63: ...specialist 3 If components of the steam humidification system are to be stored long term store them in the original packaging in a protected area 9 2 Disposal Recycling Components not used any more m...

Страница 64: ...ity of 125 1250 uS Admissible water temperature 4 30 C Admissible ambient temperature 4 30 C Admissible ambient humidity max 75 hr Max admissible duct pressure 0 8 kPa 0 8 kPa Drain temperature 60 C i...

Страница 65: ...65 Product specifications 10 2 Dimensional drawing Condair RH 22 265 467 49 163 175 75 104 131 45 98 125 118 357 130 195 135 20 G 3 4 25 Fig 16 Dimensional drawing Condair RH dimensions in mm...

Страница 66: ...Notes...

Страница 67: ......

Страница 68: ...CONSULTING SALES AND SERVICE CH94 0002 00 Condair Group AG 8808 Pf ffikon SZ Schweiz www condairgroup com...