56
Maintenance
7.4.3 Notes on cleaning the unit components
Unit component
What to clean and how to clean
Hoses
• Loosen any limescale in the hoses by carefully twisting
and flexing the hoses, then flush out the hoses thoroughly
with hot tap water.
Inlet valve
Strainer insert
• Carefully remove any limescale inside the inlet valve
and on the strainer using a soft bristled brush (do not
use a wire brush).
• Thoroughly rinse the inlet valve and the strainer insert
with fresh tap water.
Let the inlet valve dry before reinstallation!
Drain valve
• Carefully remove any limescale from the drain valve
and the valve stem using a soft bristled brush (do not
use a wire brush).
• Thoroughly rinse the drain valve and the valve stem
with fresh tap water.
Let the drain valve dry before reinstallation!
Fill cup
• Carefully remove any limescale from the fill cup and
its connectors using a soft bristled brush (do not use a
wire brush).
If fill cup is heavily calcified, place it in an 8% formic
acid solution (
observe safety notes in
until the limescale comes off.
• Thoroughly rinse the fill cup with fresh tap water.
• Reassemble fill cup.
Drain pan
• Carefully remove any limescale from the drain pan using
a soft bristled brush (do not use a wire brush).
• Then rub the drain pan with a damp cloth without de-
tergent.
Interior of the unit
(water side only)
Wipe the interior of the unit with a damp cloth without using
any cleaning agent.
CAUTION
: Take care that the electrical connections and
the electronic components remain dry!