4.5
System overviews
4.5.1 System overview Condair RH-VS
A1
B1
Condair VS
Condair RH
B2
Humidity sensor
Steam hose (DS22)
Filter valve (accessory Z261)
or
Shutoff-valve and filter 125 µm
Water supply line
(PEX reinforced hose- G 3/4"/G 3/4")
2...6 bar
4...30 °C
125 -1250 µS/cm
Drain hose,
innner diameter ø22 mm
Open funnel with trap
(by others)
Ventilation unit
HRV
Mains socket
230 V/1~/50-60 Hz
(by others)
Mains cable
(RH 1.8 only)
1)
Insulation hose EcoTherm
Air flow monitor
(external safety loop)
Maximum humidistat
(external safety loop)
Insulation
(slotted fabric hose)
Condensate hose KS10
(ø8/ø12 mm)
1)
The Condair RH 3.6 is supplied without a mains
cable and must be connected to the mains via an
electrical isolator.
Fig. 2: System overview Condair RH-VS (Example)