background image

Operation Manual

Condair HumiLife

– The proven steam solution

Condair RH

READ AND SAVE THESE INSTRUCTIONS

2

5

9

4

9

4

9

_

B

_

E

N

_

2

0

0

5

_

C

o

n

d

a

ir

-R

H

_

O

M

Humidification and Evaporative Cooling

Содержание HumiLife RH Series

Страница 1: ...Operation Manual Condair HumiLife The proven steam solution Condair RH READ AND SAVE THESE INSTRUCTIONS 2594949_B_EN_2005_Condair RH_OM Humidification and Evaporative Cooling...

Страница 2: ...r the use of parts components or equipment that are not authorized or approved by Condair CAUTION Electrical n All electrical work should be done according to all applicable local and national codes n...

Страница 3: ...ce of Operation 8 Operation 10 Starting Up 10 Shutting Down 11 Draining the Humidifier 11 Connecting to Wireless Network 11 Connecting to Condair HumiLife 11 User Interface 13 Maintenance 15 Replacing...

Страница 4: ...damaged notify the shipping company immediately l Verify the model type on the specification label to ensure that it is suitable for your installation Storage Packaging and Transportation Storage Sto...

Страница 5: ...1 Plumbing door 2 Gasket steam distributor 3 Steam distributor 4 Electrical door 5 Steam hose 6 Steam hose clamp 7 Steam cylinder 8 Steam receptacle 9 Gasket steam cylinder 10 Driver board 11 Plumbing...

Страница 6: ...flowing between submerged electrodes to generate steam VAC L1 L2 L1 higher amp draw when more of the electrode is submerged L2 lower amp draw when volume of water decreases Figure 3 Principle of Opera...

Страница 7: ...hase 1 50 60 Hz 15 Dimensions 265 mm 1 in 0 3 in 0 8 in 0 25 in 1 in 5 5 in 20 3 in 18 4 in 10 4 in 7 7 in 4 1 in 3 2 in 17 5 in 3 9 in 5 3 in 8 7 in 14 0 in 4 7 in 5 4 in 7 3 in 6 1 in 2 6 in 2 6 in...

Страница 8: ...l travel back down the hose and return to the steam cylinder Other times ex in remote installations condensate may get trapped inside a long run of steam hose In this situation a condensate return lin...

Страница 9: ...triggered If the measured amp draw is lower than the required amp draw the inlet valve is kept closed and output is reduced by letting the water level in the cylinder decrease by boiling and evaporati...

Страница 10: ...power to the unit 4 Press the power button Wait 10 minutes for the water to submerge the electrodes in the cylinder and heat up Steam will be produced if there is a demand for humidity l The humidifi...

Страница 11: ...uence refer to Shutting Down above Press and hold the power button for 2 seconds Connecting to Wireless Network Control the humidifier through the Condair HumiLife app on your wireless network Connect...

Страница 12: ...en the Condair HumiLife app You enter a screen allowing you to choose a humidifier to connect On the app press Add Device Your mobile device will begin to scan the area for the Condair HumiLife RH 4 O...

Страница 13: ...tandby The humidifier is disabled through the Condair HumiLife app The humidifier will not humidify unless it is re enabled through the Condair HumiLife app Blinking Security loop is open W2 Red Humid...

Страница 14: ...Interface 2594949_B_EN_2005_Condair RH_OM Condair RH Description Yellow Warning The humidifier will still operate but requires maintenance Red Error The humidifier stops operation to protect system co...

Страница 15: ...gs in this manual l Drain and shut down the humidifier l Use the external disconnect to remove power to the unit l Close the water supply valve l Allow the unit to cool down l Open the humidifier cabi...

Страница 16: ...maintenance or repairs on the unit WARNING Risk of severe burns from contact with hot surfaces The components in the humidifier plumbing cabinet get very hot during operation Contact with hot surface...

Страница 17: ...he cylinder out 4 Pull the cylinder out of the humidifier Caution some left over water may spill l The plumbing cover may now be removed if necessary to gain access to the hoses fill cup fill valve an...

Страница 18: ...emove the steam cylinder refer to Replacing the Cylinder on the previous page 2 Push in the tabs using a flat head screwdriver that secure the plumbing cover to the humidifier There is a tab a on the...

Страница 19: ...perly cleaned 1 2 Figure 9 Drain Valve Replacement 1 Ground connection 2 Ground fault circuit interrupter GFCI plate Removing the drain valve refer to Figure 9 above and Figure 10 on the next page 1 R...

Страница 20: ...ssemble the drain valve a Remove the solenoid from the drain valve using a Phillips screwdriver b Pull the solenoid from the core c Unscrew the core counter clockwise from the drain valve body with a...

Страница 21: ...7 Filter fill valve 8 Condensate return cap Removing the fill valve 1 Remove the cylinder and plumbing cover Remove the spade connectors from the fill valve 2 Twist off the quick connect fitting from...

Страница 22: ...amaged Note Disconnect the hoses to provide easier access to the tab 1 2 Figure 12 Removing the Fill Cup Removing and cleaning the fill cup 1 Recommended Remove hoses and clamps from the fill cup Refe...

Страница 23: ...humidity sensor If the Condair sensor supplied is being used 10 V indicates no demand and 0 V indicates full demand If another control device is used refer to the manual of that device n Check the hum...

Страница 24: ...ve changed Contact your Condair representative Steam line not installed correctly n Ensure that the distributor is oriented correctly and the steam lines if used are sloped correctly minimum 15 for st...

Страница 25: ...60 Red Unit is off but still powered Turn on the humidifier with the power button Red Yellow No WiFi connection W6 Yellow Cylinder end of life approaching expiry W5 Red Red Cylinder end of life reache...

Страница 26: ...to pulse the drain valve repeatedly while witholding voltage to the inlet valve and heating circuit However after 2 default failed attempts and if the problem persists this fault will appear and the u...

Страница 27: ...e cylinder with heating voltage If the fuse remains on 5 seconds after the heating circuit de energizes a PCB Fault is created and the unit stops humidifying This may indicate a problem with the fuse...

Страница 28: ...nd the drain valve is functioning properly Ensure that the water supply is within an acceptable range 125 1250 S cm Spent cylinder undetected The cylinder may be spent and not detected by the software...

Страница 29: ...ending on the condition of your water After this period warning W5 will upgrade to fault E5 Replace Cylinder and the unit will not operate When ordering the replacement cylinder ensure that the model...

Страница 30: ...r long term storage as follows Use a qualified service technician 1 Disconnect the humidifier from the power source 2 Disconnect the control signal inputs including any power and security loop connect...

Страница 31: ...Page intentionally left blank...

Страница 32: ...tory providing the defective part s is returned freight prepaid by the customer Parts used for repairs are warranted for the balance of the term of the warranty on the original humidifier or 90 days w...

Отзывы: