Operation
Operation | 10
2594949_B_EN_2005_Condair-RH_OM
Condair RH
Starting Up
IMPORTANT!
Damaged or improperly installed units must NOT be operated. Damaged or improperly
installed units may present a danger to persons and property.
To turn on the humidifier:
1. See the below instructions if you are starting the humidifier for the first time.
Press the power button for 2 seconds
. The unit will turn on. The unit will begin humidification
once it receives a demand for humidity.
(first time) Start Up Procedure
To start the humidifier for the first time (or after extended shut down):
1. Examine the humidifier and installation for damage or improper installation.
2. Ensure the following
before powering the unit
:
a. Ensure the cylinder is properly seated in the drain valve.
b. Ensure the front covers are in place and the electrical cover is secured with retaining
screws.
c. Ensure the water supply valve is open.
d. Ensure there is sufficient air flow through the duct.
l
Install an air proving switch, high limit humidity sensor, or wire the unit with a
furnace fan (fan activation feature) if available.
3. If a disconnect switch is installed, turn it "on" to supply power to the unit.
4. Press the power/ button. Wait 10 minutes for the water to submerge the electrodes in the
cylinder and heat up. Steam will be produced if there is a demand for humidity.
l
The humidifier will perform a self-diagnostic sequence. The LED lights and internal
components will activate temporarily during this time. After this diagnostic sequence, the
humidifier will enter normal operation.
l
If operating on low conductivity water, it may take several hours for the humidifier to
produce steam at full capacity. During this time, the humidifier will not perform any drains
(so the conductivity of the water in the cylinder may increase).
5. Check and adjust the setpoint on the humidistat for the desired humidity or temperature level
control (setpoint on the control humidistat, RH sensor, or high limit humidistat). The factory
default for the setpoint in the humidifier is 0% RH.
l
The relative humidity (RH) sensor detects the humidity of the space. If the detected
humidity is equal to or greater than the setpoint, the unit will stop humidifying. If the
humidity is less than the setpoint, humidification proceeds.
l
When the external humidistat generates a demand for humidity and the security loop is
closed, the power relay on the control board will engage, and the water fill valve will
activate (after a delay). The cylinder will fill with water.
Содержание HumiLife RH Series
Страница 31: ...Page intentionally left blank...