No airflow in the ducts
n
Check that the humidifier fan enable, terminals RF and GF, are
properly wired to the furnace.
Liquid water is found in the duct.
Installation clearances not observed
n
Outlets of the distributor tube may be too close to the duct walls.
Ensure that clearances are observed. Relocating the
distributor may be required.
Air supply temperature too low or
humidity too high
n
Indicates the design conditions have changed. Contact your
Condair representative.
Steam line not installed correctly
n
Ensure that the distributor is oriented correctly, and the steam
lines (if used) are sloped correctly:
- minimum 15° for steam moving upwards.
- minimum 2° (below horizontal) for steam moving downwards.
n
Ensure the steam line is insulated.
n
Ensure that the steam holes on the distributor are facing up.
n
Ensure that the steam distributor is installed in the supply duct.
Resetting Faults and Warnings
Error and warning codes may be reset (active faults cleared), however, if the issue has not been
resolved, the warning or error code will return.
To reset the error/warning:
1. Press and hold the power button for 3 seconds.