Mounting the nebulizers
5
Mounting the nebulizers
5.1
General information on positioning
The following
information on positioning must be referred to and complied with
:
– There must be no deflector surfaces facing in the direction of the mist. Otherwise, condensation or
precipitation – and therefore dripping water – may occur.
– The air space in front should be free at a 90° angle and a distance of 4 m.
– Within the specified free area (air space at the front, distance from ceiling and floor), there must not
be any ventilation ducts, system components or other parts / goods sensitive to humidity.
– The stubs with the high-pressure hose DN4 extending from the short T-connector (ring line) must
not be longer than 4 m.
– The nebulizers must not be placed directly over workstations or machines. In workplaces, an im-
pairment of the working environment due to evaporative cooling of the aerosols is to be expected.
Machines and materials can be damaged in the event of malfunctions due to dripping water
– Safety devices such as fire detectors or alarm systems may react to aerosol mist under certain
circumstances. This must be ruled out during installation.