33
Troubleshooting
9
Troubleshooting
9.1
Error list
NOTE!
Troubleshooting
The troubleshooting work highlighted in grey in the table may only be carried out by a Condair service
technician or authorized specialist personnel.
If the problem persists, contact your sales partner.
Fault pattern
Possible cause
Remedy
Nozzles drip
Air in the (stub) line or system.
As a rule, the zone is switched on
by the system when the target val-
ue for the measured air humidity
is fallen short of.
Perform a high pressure ring flush.
Increase or lower the target value
cyclically (1 minute operation,
1 minute pause) until the fault
pattern clears. or Cycle the zone
on and off.
Only for systems with DI water:
conductance in the (random) line
too low.
Perform a high pressure ring flush.
Increase or lower the target value
cyclically (1 minute operation, 1
minute pause) until the fault pat-
tern has been resolved. or Cycle
the zone on and off.
Only for systems with DI water:
SynPur system malfunctioning.
Check the gas pressure on the
SynPur system. This must be
at 6 bar.
Check whether errors are report-
ed via the SynPur system.
Poor spray pattern
Nozzle filter clogged.
Replace the nozzle as described
in Section 9.3.
Fan or fan openings dirty.
If necessary, clean the fan as
.
Replace the device if necessary
(see
).
Nozzles dirty.
Replace the nozzle as described
in
.