A
PPENDIX
C-1
UGH025-0504
Thermolator TW Series
TW C
ONTROL
D
EFAULT
P
ARAMETERS
Menu Function Range Default
User Level (1 sec)
SET Setpoint 20-250ºF (-6.6-121.5ºC) 75ºF
ASP Active Setpoint Read Only ºF
Configuration Level (5 sec)
Uni Unit of Measure ºF or ºC ºF
to = To Temperature
PUr Process Variable Fro = From Temperature AUG
AUG = Average Temperature
rE = Remote Temperature
SL0 = Slow
Pit Proportional Integral Tuning nor = Normal nor
FSt = Fast
dSP Deviation from Setpoint 0-45ºF (0-25ºC) 20ºF
ddt Deviation Alarm Delay Time Period 0-600 seconds
600 seconds
Ut1 Vent Time Period 1 0-999 seconds 15 seconds
Ut2 Vent Time Period 2 0-999 seconds 15 seconds
AAt Alarm Acknowledge Timer 0-60 minutes 1 minute
t01 Thermolator Version Release 01 Read Only t01
Service Level (15 sec)
SLo Slow Proportional Prop Band 0.2-180°F (0.1-100°C) 5°F
nor
Normal Proportional Prop Band
0.2-180°F (0.1-100°C) 10°F
FSt Fast Proportional Prop Band 0.2-180°F (0.1-100°C) 15°F
db Dead Band 0-10°F (0-5.6°C) 0.5°F
CCt Cooling Cycle Time 0-60 seconds 7 seconds
Ci Cooling Integral Time Period 0-999 seconds
15 seconds
HCt Heating Cycle Time 0-60 seconds 7 seconds
Hi Heating Integral Time Period 0-999 seconds 15 seconds
PrS Power-Up Restart Selector on = Manual
oFF = Auto on
rSS Remote Setpoint Selector oFF = Controller Setpoint Active
on = Remote Setpoint Active OFF
PiC Proportional to Integral
Crossover Percent 0-100% 35%
The Thermolator will not operate correctly if certain factory-set
parameters are changed. Parameters should be changed only by
qualified technical personnel who are familiar with the operation of
this type of equipment.
If the Thermolator does not appear to be working correctly, verify
the parameters against the list of factory settings.
For more detailed information about these parameters and return-
ing parameters to the initial factory setup, See the
Series 16C
Instruction Manual
included with this instruction package.
Содержание Thermolator TW
Страница 68: ...Thermolator TW Series UGH025 0504 5 16 MAINTENANCE...
Страница 102: ...Thermolator TW Series UGH025 0504 6 34 TROUBLESHOOTING...
Страница 105: ...UGH025 0504 Thermolator TW Series APPENDIX B 1 PUMP CURVES...
Страница 106: ......
Страница 108: ......
Страница 113: ...PD 1 UGH025 0504 Thermolator TW Series l TW 1 Circuit Board PD 2 l TW 2 Circuit Board PD 3 PARTS DIAGRAMS...
Страница 114: ...TW 1 CIRCUIT BOARD UGH025 0504 PD 2...
Страница 115: ...UGH025 0504 TW 2 CIRCUIT BOARD PD 3...
Страница 116: ......