Thermolator TW Series
UGH025-0504
4-16
O
PERATION
TW-1, TW-2
C
ONTROL
E
NTERING
P
ASSCODES
The TW-1 and TW-2 models have a security feature that pre-
vents accidental or unauthorized changes to the setpoint tem-
perature, high and low deviation limits, SPI address, and baud
rate.
If passcode protection is enabled, you must enter the correct
passcode to change these parameters. To enter the passcode:
Press and hold the Setpoint Select button
for 5 seconds. The control will display 1 PaS to indicate a
passcode is needed.
Press the Select
s
button until the correct
passcode appears in the display.
Press again to enter the passcode.
If the passcode is correct, the control displays ACC PAS
for 3 seconds. If the passcode is incorrect, the control dis-
plays rEJ PAS (rejected passcode) for 3 seconds.
Press Setpoint to select the parameter you
want to change.
You have access to the system parameters until:
l
The power is cycled off and on.
l
The RUN or STOP button is pressed.
NOTE:
Pressing the STOP or RUN key while you are
entering a passcode will abort the passcode entry
sequence.
1
2
3
4
Содержание Thermolator TW
Страница 68: ...Thermolator TW Series UGH025 0504 5 16 MAINTENANCE...
Страница 102: ...Thermolator TW Series UGH025 0504 6 34 TROUBLESHOOTING...
Страница 105: ...UGH025 0504 Thermolator TW Series APPENDIX B 1 PUMP CURVES...
Страница 106: ......
Страница 108: ......
Страница 113: ...PD 1 UGH025 0504 Thermolator TW Series l TW 1 Circuit Board PD 2 l TW 2 Circuit Board PD 3 PARTS DIAGRAMS...
Страница 114: ...TW 1 CIRCUIT BOARD UGH025 0504 PD 2...
Страница 115: ...UGH025 0504 TW 2 CIRCUIT BOARD PD 3...
Страница 116: ......