22 - Hardware Installation
DeviceMaster Installation and Configuration Guide
: 2000594 Rev. F
Hardware Installation
DM-2304: 4-Port DIN Rail (DB9) Installation
Use the following procedure to install DM-2304.
1.
Attach the DeviceMaster to the DIN rail adapter.
2.
Connect the power supply and apply power to the DeviceMaster using the power supply specifications on
the product label and the following information.
Observe proper ESD techniques when connecting and disconnecting the
DeviceMaster
.
a.
If the DIN rail is not connected to earth ground,
insert the earth ground wire into the chassis
ground screw terminal.
Note:
The chassis ground connection is made only if
the DIN rail is NOT connected to earth ground.
b.
Insert the DC positive wire into one of the + screw
terminals and the DC return wire into the - screw
terminal.
• A second redundant power supply can be
connected to the unit by inserting the DC
positive wire into the other + screw terminal and
the DC return wire into the - screw terminal.
• The DeviceMaster continues to operate if one of
the two connected power supplies should fail.
DM-2304: 4-Port DIN Rail Models Power
on Page 144 for detailed power
requirements.
c.
Use a small flat head screw driver to lock the wires into place.
d.
Verify that each wire has been tightened securely.
e.
Connect a UL Listed power supply and UL Listed power cord to a power source to apply power.
Note:
Do not connect multiple units until you have changed the default IP address, see
3.
Connect one of the
10/100
ports to the same Ethernet network segment as the host PC using
a standard
Ethernet cable. You can daisy-chain another DeviceMaster or Ethernet device to the other port using a
standard Ethernet cable.
4.
Verify that the
Status
LED has completed the boot cycle and network connection for the DeviceMaster is
functioning properly using the following table.
DM-2304 LED Descriptions
STATUS
The
STATUS
LED on the device is lit, indicating you have power and it has completed the
boot cycle.
Note:
The
Status
LED flashes while booting and it takes approximately 15 seconds for the
Bootloader to complete the cycle.
When the Bootloader completes the cycle, the LED
has a solid, steady light that blinks approximately every 10 seconds
.
LINK
If the
LINK
(green) LED is lit, it indicates a working Ethernet connection.
ACT
If the
ACT
(yellow) LED flashes, it indicates network activity.
Note:
For additional LED information, go to the
on Page 148.
Caution
† Wire gauge: AWG 12-22
PW1
PW2
Chassis
Ground†
Return†
Positive†
Positive†
5-30VDC
5-30VDC
Содержание DeviceMaster PRO
Страница 1: ...Installation and Configuration Guide ...
Страница 32: ...32 Hardware Installation DeviceMaster Installation and Configuration Guide 2000594 Rev F Hardware Installation ...
Страница 130: ...130 Managing the DeviceMaster DeviceMaster Installation and Configuration Guide 2000594 Rev F Managing the DeviceMaster ...