Statox 502 Control Module
Page 22 of 40
Issue 1/2015
1.
Enter the menu „SENSOR POWER“ by pushing
.
2.
Display „SENSOR ON“.
Up to step 7 the automatic Time-out is not active.
3.
Change the status of the sensor head power supply with
◄
-
or
►
.
4.
Confirm with Enter.
5.
„SENSOR OFF“ flashing tells you that the sensor head power supply is off.
6.
Push
to switch the power supply on again.
7.
„SENSOR ON“ tells you that the sensor head power supply is on.
8.
Push Reset to return to the main menu and again to return to measuring mode.
Programming the alarm relays
In this menu you can set parameters of the alarm relays A1 and A2:
1.
Alarm thresholds
2.
High or low alarm
3.
Latching (HOLD) or non-latching (AUTO RESET)
4.
Coil active (ACTIVE) or non-active (PASSIVE)
If an alarm threshold is exceeded, the LEDs A1 and A2 are on, and the relays switch. Alarms can be reset,
provided the reason for the alarm has disappeared. If the alarms have been programmed to be latching, you
have to push reset button or use the external reset to delete the alarm message. For additional information
see chapter 4.5.1.
!