Statox 502 Control Module
Issue 1/2015
Page 15 of 40
Main menu structure
After pushing
◄
-
and
►
-button together for 2 s and entering the password, you have access to the main
menu. It is structured as a ring with 9 different submenus in which you can set parameters or perform a
calibration. See
Figure 11
. Pushing the Reset–button always brings you back into the measuring mode.
Figure 11: Main menu structure
Submenu
Description
Page
CHOOSE PROGRAM
1)
Selecting the appropriate program for the relevant sensor head
16
CALIB. ROUTINE
1) 2)
Calibration with gas
18
BRIDGE VOLTAGE
1) 2)
Monitoring the bridge voltage in mV
20
SENSOR POWER
1) 2)
Switch the sensor power supply off
21
OUTPUT TEST
Test of the LEDs, relays, alarms and the analog output
26
SERVICE OUTPUT
Setting of the analog output in the service mode
28
MODE
Altering the operation mode (Common Alarm Module or Control Module)
29
ALARM 1 RELAY
Setting Alarm 1 relays parameters
23
ALARM 2 RELAY
Setting Alarm 2 relays parameters
23
1)
no access if the Statox 502 is operated as Common Alarm Module.
2)
no access if a program for the operation of Statox 501/S, Statox 501 Infratox and Statox 505 is active.
„MENU NOT ACTIVE“ will be shown for 2 s if a menu is not accessible in the actual mode or
program.
!
MEASURING MODE