background image

 
Revision: 01 02/29/2016 

Page 15 

 

 
(1) Check electrical components and tighten any loose connections. 
(2) Check all wiring and electrical insulators. 
(3) Check contactors to ensure proper operation and contact point for wear. 
(4)  Check  that  fan  motors  (if  applicable)  are  operational,  ensure  fan  blades  are  tight  and  all 
mounting bolts are tight. 
(5) Ensure that the condenser surface (if applicable) is cleaned and free of dirt and debris. 
(6) Check the operation of the control system. Make certain that all of the safety controls are 
operational and functioning properly. 
(7)  Check  chilled  water  valve  system.  Make  sure  that  all  mechanical  joints  and  flare  nuts  are 
tight. 

Service Parts Availability 

Genuine replacement service parts should be used whenever possible. Parts may be obtained 
by contacting your local sales representative or authorized distributor. Contact us 562.945.8971 
 

TROUBLESHOOTING

 

GUIDE 

 

Complaint 

 

Problem 

 

Symptom 

 

Action 

1.

 

 

Chilled water valve is 
not opening because of 
loose or broken wiring. 

Display shows chilled 
water cooling is on or 
economy cooling is on 
but, the valve is closed. 

Test for 24VAC at valve 
motor. Check continuity 
between chilled water 
pins connection of the 
microprocessor 
controller and valve 
motor. If no voltage, 
replace microprocessor 
setting. (refer to 
supplied controller 
manual-by other) 

2.

 

System does 
not humidify 
or does not do 
so sufficiently. 

Control parameters are 
not set correctly or set 
as expected.  

System seems to 
function okay 
otherwise. 

Refer to controller 
setting and check that 
all control parameters 
are set correctly. 

 

Loose or broken wiring 
in low voltage circuits or 
bad microprocessor 
board. 

Display shows 
humidification 
operating but, the 
humidifier is not on. 

Test for 24VAC at pin 
connetion on controller. 
If no voltage, check 
wiring back to system.  

3.

 

System is on 
but, no-thing 
is operating. 
The blower is 
off. 

No air flow, fire stat, 
water on floor or smoke 
detector alarm is 
activated. 

The display shows one 
or more of these alarms 
and the Alarm LED is on. 

The system is 
automatic-ally shut 
down if any of these 
conditions occur. 
Determine what the 

Содержание CKC AYAN IV-IR NANO SERIES

Страница 1: ...ONAL MAINTENANCE MANUAL IN ROW NANO SYSTEMS CKC AYAN IV IR NANO SERIES IN ROW COOLING COMPU AIRE INC 8176 BYRON ROAD WHITTIER CA 90606 PHONE 562 945 8971 FAX 562 696 0724 Website ww compu aire com Ema...

Страница 2: ...6 IMPORTANT SUGGESTION 6 ABOUT COMPU KOOL AYAN IV SERIES 6 TECHNICAL DATA 7 INSTALLATION 8 UTILITY CONNECTIONS 8 AIR FLOW 8 CONNECTIONS 8 STRUCTURAL SUPPORT 8 ELECTRICAL SUPPORT 9 CONDENSATE DRAIN CO...

Страница 3: ...s manual Follow all local codes and safety requirements to install and service this unit WARNING Installation and service of this equipment should be done by qualified personnel who have been speciall...

Страница 4: ...tern of inhibitor depletion GENERAL The Compu Aire Compu Kool Ayan IV In Row Nano series is a complete environmental control system factory wired tested and specially designed to provide temperature h...

Страница 5: ...nd servicing the unit Front and rear of the unit should have a minimum clearance of 36 inches for servicing The unit you have received is very special It is specifically designed for Computer Room app...

Страница 6: ...please call COMPU AIRE INC at 562 945 8971 ABOUT COMPU KOOL AYAN IV SERIES The COMPU KOOL AYAN IV SERIES is designed to provide localized temperature and humidity control in high heat load areas found...

Страница 7: ...apacity BTU HR 94 186 Leaving Coil 67 FBD 58 2 FWB CHILLED WATER COIL DATA Aluminum Fins 3 8 OD Copper tubing Face Area Sq Ft 5 35 Rows FPI 3 12 CHILLED WATER DATA At 45 F Entering Water Temp 55 F Lea...

Страница 8: ...panel and piping connection could be brought from the rear top panel of the unit Provide isolation shut off valves for all pipes external to the unit AIR FLOW The return air is drawn through the back...

Страница 9: ...and dry fluid cooler for the glycol cooled units CONDENSATE DRAIN CONNECTION A submersible water pump is placed on the drain pan and will active when the pump detect water condensation and pump the wa...

Страница 10: ...Revision 01 02 29 2016 Page 10 FIGURE 1 SYSTEM LAYOUT...

Страница 11: ...Revision 01 02 29 2016 Page 11 Wiring Diagram FIGURE 2 GENERAL WIRING DIAGRAM 628 450 111 MCP SYSTEM 2200 CA 9362 COOL ONLY AYAN IV NANO...

Страница 12: ...Revision 01 02 29 2016 Page 12 FIGURE 3 AYAN IV INROW COOLING Figure 4 Front view Return Air Inlet Leveling Feet Graphical Display Supply Air Supply Air Ecofit Fan EC Motor Supply Grille Locking latch...

Страница 13: ...5 BACK VIEW FIGURE 6 CONTROL PANEL Current Sensor Transformer Aux Relay Terminal Block Chilled Water Coil Chilled Water Valve Actuator Piping Connections SMOKE DETECTOR Electrical Control Panel Micro...

Страница 14: ...enance must be performed in regular intervals to provide continued operation of the entire unit The maintenance intervals must be determined site specifically Use the maintenance checklist at the end...

Страница 15: ...is not opening because of loose or broken wiring Display shows chilled water cooling is on or economy cooling is on but the valve is closed Test for 24VAC at valve motor Check continuity between chil...

Страница 16: ...eset button on the controller 4 System does not run No 24VAC supply voltage Power LED is not on Check circuit breaker in system 24VAC circuit and reset if necessary Check System cutout switch Test for...

Страница 17: ...rvice such as replacing filters humidifier cylinder infra red lamps float valve assemblies belts cleaning lubrication calibration and adjusting are NOT INCLUDED in this warranty Replacement or repair...

Страница 18: ...E NUMBER FAX NO EMAIL TECHNICIAN S NAME TECHNICIAN PHONE NO PROJECT NAME PROJECT ADDRESS CUSTOMER CONTACT UNIT MODEL UNIT SERIAL NO VOLTAGE UNIT TYPE CHILLED WATER AIR HANDLER UNIT EQUIPPED WITH TYPE...

Страница 19: ...I LOW TEMPERATURE AND HUMIDITY SET POINTS NOTE ANY CHANGES MADE TO THE CONTROLLER SETTINGS UNIT POWER SUPPLY Test Voltage LINE VOLTAGE L1 L2 L2 L3 L1 L3 CONTROL VOLTAGE AT CONTROLLER ___________ evap...

Страница 20: ...L3 VERIFY FILL VALVE OPERATION ____________________ DRAIN VALVE OPERATION ___________________________ CONDITION in 100 cooling TEST mode SUPPLY AIR TEMPERATURE F RETURN AIR TEMPERATURE RETURN RETURN A...

Страница 21: ...OUT PUTS Alarm set points TEMPERATURE HIGH ___ LOW HUMIDITY HIGH ___ LOW NOTE ANY CHANGES MADE TO THE CONTROLLER SETTINGS Condensate Pump WET TEST ___ TECHNICIAN COMMENTS NOTE ALL READINGS AND ANY AD...

Страница 22: ...8971 Phone 1 562 696 0724 Fax While every precaution has been taken to ensure the accuracy and completeness of this literature Compu Aire assumes no responsibility and disclaims all liability for dam...