Revision: 01 02/29/2016
Page 19
WIRES FOR CONNECTION TIGHTNESS
UNIT GROUND CONNECTED
HIGH AND LOW VOLTAGE WIRING CONDITION FOR ANY DAMAGE
EC FAN MOTOR ASSEMBLY
SMOKE DETECTOR
REMOTE SENSORS
CONDENSATE PUMP MOUNT
PIPING AND VALVE SUPPORTS AND AVOID ANY RUBBING PIPES
INSULATION (CHECK ALL PIPING, C.W. VALVES)
CONDENSATE DRAIN TRAP
ISOLATION VALVES INSTALLED
STRAINER INSTALLED
SUPPLY AND RETURN AIR CLERANCE AND AIR DISTRIBUTION
HUMIDIFIER WATER LINES FLUSHED
HUMIDIFIER CYLINDER IS SECURED
CHILLED WATER VALVES IS SECURED
SET CONTROLS to test operation:
TEMPERATURE SET POINT
HUMIDISTAT SETPOINT
HI LOW TEMPERATURE AND HUMIDITY SET POINTS
(NOTE ANY CHANGES MADE TO THE CONTROLLER SETTINGS)
UNIT POWER SUPPLY: Test Voltage
LINE VOLTAGE: L1-L2:
L2-L3:
L1-L3:
CONTROL VOLTAGE AT CONTROLLER: ___________
evap fan #1
MOTOR HP/KW:
F.L.A:
VOLTAGE:
MODEL # ___________________________________________________________________
AMP DRAW: L1
L2
L3
CONTROL INPUT SIGNAL MIN/MAX:
VDC
evap fan #2
MOTOR HP/KW:
F.L.A:
VOLTAGE:
MODEL # ___________________________________________________________________
AMP DRAW: L1
L2
L3
CONTROL INPUT SIGNAL MIN/MAX:
VDC
evap fan #3
MOTOR HP/KW:
F.L.A:
VOLTAGE:
MODEL # ___________________________________________________________________
AMP DRAW: L1
L2
L3
CONTROL INPUT SIGNAL MIN/MAX:
VDC
evap fan #4
MOTOR HP/KW:
F.L.A:
VOLTAGE:
MODEL # ___________________________________________________________________