Preparing the Server
Optimum Environment
When installing your ProLiant 6400R server in a rack, temperature standards
and power requirements must be met.
Space Requirements
Consider the following when deciding where to install your Compaq rack:
■
Clearance in the front of the rack should be a minimum of 25 inches for
servicing.
■
Clearance in the back of the rack should be a minimum of 30 inches for
servicing and adequate airflow.
Power Requirements
WARNING:
To reduce the risk of personal injury, fire, or damage to the
equipment, do not overload the AC supply branch circuit that provides power to
the rack. Consult the electrical authority with jurisdiction over your facility wiring
and installation requirements.
IMPORTANT:
Because of the 100- to 120-VAC electrical rating of each power supply,
some local electrical authorities may require either one 15-A circuit for each power supply
or one 20-A circuit for each pair of power supplies.
■
The power load must be balanced between available AC supply branch
circuits.
■
The overall system AC current load must not exceed 80 percent of the
branch circuit AC current rating.
■
If power strips are used, the load should not exceed 80 percent of the
marked electrical current rating on the power strip.
The installation of the equipment must comply with local and regional
electrical regulations governing the installation of information technology
equipment by licensed electricians. The equipment is designed to operate in
installations covered by the National Electric Code (ANSI/NFPA 70, 1993).
The equipment is also designed to operate in installations covered by the code
for the Protection of Electronic Computer/Data Processing Equipment (NFPA-
75, 1992).