ADCP-90-606 • Rev C • May 2020
Page 48
© 2020
CommScope
. All Rights Reserved.
b. Remove the connector dust cap and clean the MPO connector as specified in the
Multifiber-Push On Assembly Connector Cleaning Instructions (ADCP-96-150).
c. Connect the microcable MPO connector to the appropriate equipment MPO
connector. Labels are attached to each microcable, as shown in
d. When all the microcable MPO connectors are connected to the equipment MPO
connectors, proceed to step 14.
11. Complete the following for each stub end microcable terminated with a non-functional
connector:
Figure 61. Cable Number and Optical Port Designation Labels
a. Record the label information (cable number, range of optical ports, and serial number)
that is applied to each cable and then tag each cable so it can be identified when the
cable jacket is removed for splicing.
b. Cut off the non-functional connector and discard.
c. Determine the point at which the microcable will be attached to the splice tray and
then strip back the cable jacket to expose the optical fibers.
Note:
Do not cut off the non-functional connector before cable installation has been
completed or the integrity of the cable may be compromised.
1
1 - 12
13 - 24
2
24155-B
1
1 - 12
13 - 24
2
CABLE
NUMBER
PORT
DESIGNATION
LABELS