7. Determine whether the cable will be routed through a trough or conduit, and select the
corresponding procedure in
. Following the instructions provided, route
the microcable to as close as possible to the appropriate ODF or fiber panel, then return to
to mount the panel shell on the equipment rack.
6.2
Mounting the Panel Shell on the Equipment Rack
Use the following procedure to mount the panel.
1. Select a suitable location for mounting the panel shell in the rack. Provide a minimum of
15 inches clearance at the front or rear for installing the RapidReel cable spool tray.
2. Remove the panel shell from the shipment box (see
3. Determine if the rack or cabinet width is 19 or 23 inches. Also, determine recess required
(2, 4, or 5 inches) for mounting the panel. Refer to
Figure 36. Mounting Bracket Installation (3RU Panel Shell Shown)
4. If the panel is being installed in a 23-inch rack or cabinet in other than the 5-inch recess
position, remove the 23-inch mounting brackets and re-install them at the required (2- or
4- inch) recess position. Tighten screws to the torque specification shown in
Note:
Due to space constraints in conduit, only cables with MPO connectors or MPO-like
non-functional connectors should be routed through conduit.
Note:
After the cables have been completely unwound from the external spool, an
additional length of up to 200 feet of cable will be left on the RapidReel cable spool.
Note:
When the microcable has been completely unwound from the external spool, STOP
ROTATING THE SPOOLS.
Note:
The Rapid Fiber Panel is designed to be installed in an environmentally controlled
network telecommunications facility such as a Central Office, Controlled Environmental
Vault, or Data Center. Only the I/O cable is rated for both indoor and outdoor use.
Note:
If a Rapid Fiber Panel is installed above or below a non-Rapid fiber panel, 1RU of
open space must be left between the panels. This space is required for accessing the rear
connectors if cleaning is required.
BRACKET FOR
23-INCH RACK
BRACKET FOR
19-INCH RACK
5-INCH
RECESS
4-INCH
RECESS
26200-A
2-INCH
RECESS
NOTE: APPLY 15 INCH-POUNDS
1.7 NM) OF TORQUE