Functions & configuration

EB8E4A

14

1.0/0315

“Call park” function

In order to avoid that the cell call is cancelled after it had been answered, this call can be “parked” by
pressing button 

3

 at the control desk. Therefore, the call will be kept at the control desk (but without

an acoustical buzzer signal). By pressing 

X

, a conversation can be built up again. When the conversa-

tion is cancelled with 

X

 or 

F

, the “call park” function is cleared. 

 

Attendance function

The key switch in front of the prison cell activates the function “attendance”. The key switch has to be
connected to two inputs at the EB8E4A (“E1” to “E8”).

The system cancels an initiated officer emergency call (with “cancel on site” and “clear emergency call
only after acknowledgement”) by activating the attendance function only when already a conversation
to the respective inquiry station had been built up. 

Carry out the following configuration in CCT 800 to activate the function “attendance”:

Select 

Subscriber > Station properties > ET808 family > EB8E4A > # - Station # > Security

>

 tab 

Key-switch

.

In the drop-down list 

Key-switch

, define the required option of the two previously selected inputs

for “attendance 1” and “attendance 2” (“Key-switch (standard)”, “Key-switch with Flag-contact”,
“Key-switch with attendance lamp”, “Key-switch with Flag and attendance”, “Key-switch (push but-
ton)”, “Key-switch (push button) with Call Park output”, “Key-switch (push button) with attendance
lamp” or “Key-switch (push button) with Flag and attendance”).  

In the drop-down list 

Simulated input no.

, define the inputs (“IN1” to “IN3”) for the input message

to which the attendant contacts for the call park lamp or attendance lamp are connected. 

In the drop-down list 

Attendance monitoring [sec]

, define the time in seconds after which the sys-

tem has to initiate an officer emergency call at “attendance 2”.

Select the option “none” for the input “attendance 1”, as there will be no officer emergency call
initiated automatically.

For the input “attendance 2”, select the required time in seconds after which an officer emergency
call has to be initiated automatically (“15”, “30”, “120” or “180”).

Define any unused input for the initiation of an officer emergency call after a beforehand-defined
time (without an additional call button). This input has to be configured with the function “officer
emergency call”. For further information regarding the configuration of officer emergency calls, 

see

”Officer emergency call” on page 13

Note:

For activation of the “call park” function with button 

3

, no configuration is required.

Note:

The key switch can be switched into two different positions:

“Attendance 1”: The system gets the information that an attendant is present in the cell.

“Attendance 2”: The system gets the information that an attendant is present in the cell. Additionally, a 
timer will be activated, so that an attendant must make a report to the control desk in the defined time, 
otherwise the system initiates an officer emergency call automatically. 

Note:

For the activation of a call park lamp and/or an attendance lamp, the required option with the respective 
additional instruction (e.g. “… with Flag-contact”) has to be selected in the drop-down list 

Key-switch

Содержание C-EB8E4A

Страница 1: ...PRODUCT MANUAL ENGLISH EB8E4A VERSION 1 0 0315 ...

Страница 2: ...ices The equipment has to be connected to an SELV LPS circuit only SELV safety extra low voltage see IEC EN 60950 1 LPS limited power source see IEC EN 60950 1 The equipment may not be exposed to high temperatures see Technical data on page 5 Manufacturer s reference This equipment fulfils the requirements of the EU directive 2004 108 EC EMC This equipment fulfils the requirements of the EU direct...

Страница 3: ...nctions in front of the cell 5 Installation 6 Connection diagram 6 Dimensions 7 Power supply 8 Functions configuration 9 Basic settings 9 Inputs and outputs 9 Input functions 10 Prison cell call officer emergency call 12 Attendance function 14 Sabotage 15 Light 16 Offline operation 19 Additional features 20 Technical support 21 ...

Страница 4: ...nce in the cell Easy connection of I O contacts by means of the removable screw terminals In case the server is unavailable the EB8E4A option module still recognises the presence of a custodian in the cell identifies cell and emergency calls and detects sabotage attempts Protection against vandalism and sabotage alert In case the EB8E4A option module is unavailable the ET 808A Intercom module info...

Страница 5: ...hes push buttons relay outputs etc Attention For the switching position ON the switch resistance has to be less than 1 kΩ Outputs 4 x relay outputs 2 x changeover and 2 x NO contacts 30 V 1 A 200 000 make and break cycles 30 V 2 A 100 000 make and break cycles Operating temperature range 20 C to 60 C 4 F to 140 F Operating temperature range 20 C to 60 C 4 F to 140 F Plugs 2 x expansion bus 7 x scr...

Страница 6: ...AC Without enclosure power supply option B 26 VDC 6 VAC The switching power must not exceed 60 W 62 5 VA 2 A For further information regarding the power supply see Power supply on page 8 Attention The module as well as all outputs may only be connected to a SELV LPS circuit GND OUT4 OUT4 GND GND IN6 IN5 IN4 IN3 IN2 IN1 OUT1 OUT2 IN8 OUT 24 VAC IN7 L2 L1 F OUT3 OUT3 Ribbon cable to ET 808A Relais P...

Страница 7: ...scale Notes The module depth with components is 15 mm 0 59 inch For use of an EB8E4A together with an ET 808A the EB8E4A has to be broken at the break off notch 90 3 55 80 3 15 60 2 36 120 4 73 130 5 12 65 2 56 55 2 17 Break off notch 4 x ø 3 2 0 13 3 x ø 6 0 24 6 x ø 4 0 16 ...

Страница 8: ...ge of 5 VDC For further information regarding the power supply of the ET 808A see Datasheet ET 808A Option B 24 VAC via I O connector The option module EB8E4A transmits the supply voltage via the I O connector to the Intercom module ET 808A and receives a voltage of 5 VDC from the ET 808A EB8E4A ET 808A 12 24 VAC 15 30 VDC 5 VDC Converter EB8E4A ET 808A 24 VAC 24 VAC 5 VDC Converter ...

Страница 9: ...as well as OUT2 are designed as NO contacts and OUT3 as well as OUT4 are de signed as changeover contacts The eight digital inputs can be used for all features which are shown at Subscriber Station properties EB8E4A Three inputs IN1 to IN3 of them are available for additional features e g for input messages or dialling simulations These three inputs can be linked with the screw ter minals from E1 ...

Страница 10: ...puts tab Input simulation In the drop down list Simulated input no define the desired input IN1 to IN3 In the drop down list Simulated level at active input define the level that is processed in the In tercom Server at an active input Short 1k5 5k6 15k Break In the drop down list Simulated level at inactive input define the level that is processed in the Intercom Server at an inactive input Short ...

Страница 11: ...te a repetition lock Therefore a time interval can be defined in which only a certain number of calls can be initiated to pre vent repeated calls Carry out the following configuration in CCT 800 to activate a repetition lock Select Subscriber Station properties ET808 family EB8E4A Station tab Gen eral settings In the drop down list Interval s define the desired time interval in seconds 1 2 4 8 16 ...

Страница 12: ...ck so that there is no chance to initiate a new call e g for 30 seconds after three calls had been initiated in a row For further information see Repetition lock for inputs on page 11 The system indicates cell calls as normal calls with a long buzzer interval The cell call can be cancelled either by answering the call building up a conversation or by the attendance function see Attendan ce functio...

Страница 13: ...tact for switching the cell lamp at call requests For this activate the internal output of the EB8E4A at Subscriber Station properties ET808 family EB8E4A Activate the field Quittierung offline if an offline acknowledgement of a cell call is required Define the functions of the key switch For further information see Attendance function on page 14 Prison cell calls with officer emergency calls Pris...

Страница 14: ...p down list Simulated input no define the inputs IN1 to IN3 for the input message to which the attendant contacts for the call park lamp or attendance lamp are connected In the drop down list Attendance monitoring sec define the time in seconds after which the sys tem has to initiate an officer emergency call at attendance 2 Select the option none for the input attendance 1 as there will be no off...

Страница 15: ...essage to the control desk Select Subscriber Station properties ET808 family EB8E4A tab Inputs Activate the respective input IN1 to IN3 Select Inputs Input message tab Triggering Right click on the cell terminal and select add Input message In the drop down list 15k choose Idle and in the drop down list 1k5 choose Active 2 Configure the input in CCT 800 on which the sabotage contact is connected a...

Страница 16: ...off and the light button is out of order see Light withdra wal on page 18 Additionally a repetition lock can be configured For further information regarding the function repetition lock see Repetition lock for inputs on page 11 Carry out the following configuration in CCT 800 to activate the function light switch in the cell Select Subscriber Station properties ET808 family EB8E4A Station Light ta...

Страница 17: ... indication of state The status of the light can be read in via an input of the EB8E4A It is possible to indicate the status in the following ways is not required when using a relay Indicator control desk message The control desk indicates the input as input message Indicator COMWIN Via an ICX message the light state can be inquired The system answers with a message of which two digits TT can be f...

Страница 18: ...vated after switching attendance the latching relay will be ener gised every ten seconds until the input is activated Light withdrawal Light permanently on Commands from the Intercom Server Task Type Parameter 1 Parameter 2 Activate light withdrawal 45 7E Call number cell 9004 Deactivate light withdrawal 45 7E Call number cell 9005 Retrieve light withdrawal status 45 7E Call number cell 9006 Messa...

Страница 19: ...If the prisoner initiates an emergency call in offline operation the lamp in front of the cell does not light permanently but blinks in one second intervals also applies for online operation This ensures that emergency calls will be indicated in front of the cell if the Intercom Server is not available As soon as a connection between the cell terminal and the Intercom Server is established the sys...

Страница 20: ...a connection between the cell terminal and the Intercom Server is established the last switched state in the cell will be active Offline output configuration The outputs of the EB8E4A are provided for the following functions and can not be modified OUT1 Call lamp OUT2 Call park lamp OUT3 Attendance OUT4 Cell light Additional features Firmware download The firmware of the EB8E4A is downloadable in ...

Страница 21: ...EB8E4A Technical support 1 0 0315 21 Technical support For more information about our products and services please visit www software manuals com ...

Отзывы: