 l

oCation

Locate the control on a vibration-free inside wall in an area having good air circulation. 

The  control  should  be  located  approximately  five  feet  high.  The  control  should  be 

located in an area such that it is not influenced by the following:

  Drafts

  Dead spots behind doors, in corners, or under cabinets

  Cold or hot air from registers

  Sunlight

  Light from fixtures or other appliance

  Radiant heat from a fireplace or other heat source

  Concealed water pipes (hot or cold)

  Unconditioned areas behind the control

NOTE:

 It is recommended that multiple wires into a single terminal be twisted together prior to inserting into the plug 

connector. Failure to do so may result in intermittent operation.

W

iring

 r

eQuirementS

Each  digitally  communicating  device  in  the  system  requires  four  wire  connections: 

24VAC Hot (R), 24VAC Common (C), Data 1 (1), and Data 2 (2). The R and C connections 

provide a 24VAC power supply that can be shared between the indoor and outdoor units 

and the thermostat. The data 1 and data 2 connections provide the communications bus 

between the indoor unit, outdoor unit and thermostat. Thus, the R, C, 1, and 2 terminals 

must be wired consistently. See the indoor unit and outdoor unit respective installation 

manuals for additional wiring details.

S

enSorS

Sub-menu Item

Indication/User 

Modifiable Options

Comments

Outdoor Air  

Temperature 

(AIR TMP)

Displays the outdoor 

air temperature

Sensor may or may not be available  

on an air conditioner. Check air  

conditioner instructions for details.

Outdoor Coil Tem-

perature (COIL TMP)

Displays the outdoor 

coil temperature

Required for heat pump operation.

C

ool

 S

et

-

uP

Sub-menu Item

User Modifiable 

Options

Comments 

(applies to AC and HP models)

Cool Airflow Trim 

(CL TRM)

-10% to +10% in 2% 

Increments

Selects the airflow trim amount;  

applies to air conditioner only.

Cool Airflow Profile 

(CL PRFL)

A, B, C, or D

Selects the airflow profile; applies to 

air conditioner only.

Cool ON Delay  

(CL ON)

5, 10, 20, or 30 

seconds

Selects the indoor blower on delay; 

applies to air conditioner only.

Cool OFF Delay 

(CL OFF)

30, 60, 90, or 120 

seconds

Selects the indoor blower off delay; 

applies to air conditioner only.

Dehumidification 

Select (DEHUM)

ON or OFF (default 

is OFF)

Selecting “OFF” disables dehumidification; 

selecting “ON” enables dehumidification; 

applies to air conditioner only.

  Indoor  unit  to  thermostat  wiring: 

Connect a wire between terminal “R” on 

the  thermostat  sub  base  and  terminal 

“R” on the 4-position plug connector for 

the indoor unit. Repeat for the C, 1, and 2 
terminals. 

  Indoor  unit  to  outdoor  unit  wiring: 

Connect  a  wire  between  terminal  “R” 

on the indoor unit’s 4-position plug and 

the  terminal  “R”  on  the  outdoor  unit’s 

4-position  plug  connector.  Repeat  for 

the C, 1, and 2 terminals. 

Touchscreen

Thermostat

Indoor

Board Terminal

Connections

Outdoor

Board Terminal 

Connections

R

C

1

2

R

C

1

2

R

C

1

2

24VAC (Hot)

24VAC

(Common)

Data 1

Data 2

Содержание CTK01

Страница 1: ...INSTALLATION POWER UP SETUP USAGE GUIDE ADVANCED MENUS Installation and Start Up Instructions An Exclusive Touchscreen Control Featuring Serial Communication Model CTK01...

Страница 2: ...el applications dehumidification filter maintenance reminders outdoor temperature display and advanced menus The various options and display areas are described below FAILURE TO READ AND FOLLOW ALL IN...

Страница 3: ...r Up 9 Power Up 9 Thermostat Messages 9 Auto Configuration 9 Check System Operation 10 Thermostat Set up 11 Set Current Time and Day 11 Choose the System Setting 12 Energy Saving Factory Program 12 Th...

Страница 4: ...s communicating control kit contains the following components 1 Communicating touchscreen control with sub base 1 230 VAC to 24 VAC 40 VA transformer B1141643 2 Tyco 284041 4 4 position plug color cod...

Страница 5: ...ry tag to prevent power drainage The battery tag must be removed to engage the batteries The batteries are required to maintain time during a power outage They are also required for armchair programmi...

Страница 6: ...system requires four wire connections 24VAC Hot R 24VAC Common C Data 1 1 and Data 2 2 The R and C connections provide a 24VAC power supply that can be shared between the indoor and outdoor units and...

Страница 7: ...r to the 240VAC COM terminal on the transformer Connect the other end of the wire jumper to L2 on the outdoor unit s control Connect the terminated end of the red 14 wire jumper to the 24VAC terminal...

Страница 8: ...stat Pull the thermostat body off the thermostat base Forcing or prying on the thermostat will cause damage to the unit Place base at installation location and mark mounting hole locations on wall usi...

Страница 9: ...hat the equipment has been found with the message equipment FOUND Auto Configuration The system will auto configure itself once all system components have been identified The result is that the system...

Страница 10: ...ng Heating System Press Run Schedule Press to adjust thermostat setting above room temperature The heating system should begin to operate Press to adjust thermostat setting below room temperature The...

Страница 11: ...isplay Touch either the or key until you reach the correct hour and AM or PM designation Then touch Set Time again to display min utes only in clock display Touch and hold either the or keys until you...

Страница 12: ...system Em Emergency setting available only when the thermostat detects a heat pump in the system Auto Auto Changeover is used where both heating and cooling may be required during the same day Auto al...

Страница 13: ...cation setting Default is OFF It can be set in the range of 40 to 94 Above 94 is the OFF setting Ideally the indoor humidity should be set in the range of 40 to 60 When On Demand Dehumidification is s...

Страница 14: ...nged to 0 Days to indicate no programs will be run When set for 7 Days the thermostat will follow the factory program or the program that you entered Select Energy Management Recovery Scrolling Messag...

Страница 15: ...ht will turn on momentarily Select temperature offset Scrolling message will show TEMPERATURE ADJUSTMENT Default is 0 with current temperature Adjustment can be made from 5 Lo to 5 HI to change the di...

Страница 16: ...air filter maintenance reminder Scrolling message will show AIR FILTER MAINTENANCE Default is OFF It can be changed to a setting from 25 to 1975 hours in increments of 25 hours to select the amount of...

Страница 17: ...may be required on the same day Auto allows the thermostat to automatically switch between heating and cooling operation Auxiliary Heating When the thermostat is configured for Heat Pump mode and an...

Страница 18: ...the screen Touch the Hold key to maintain the new set point temperature Hold At will display to the left of the temperature set point To cancel the permanent hold setting at any time and return to th...

Страница 19: ...period The display will show FAN On Prog Check System Status If the Home Screen Display indicates Call for Service and Check Equipment Name inthescrollingmessagearea there is a fault in the system Whe...

Страница 20: ...Installer Config key again for approximately 3 seconds to enter the Advanced Installer Configuration menu 1 2 Fault Status The display will change to the Fault Screen indicating any faults that may b...

Страница 21: ...to enter that equipment sub menu listing The scrolling message area will show WORKING to indicate that the thermostat is retrieving data Then the first equipment sub menu name appears in the scrolling...

Страница 22: ...ange is accepted If the change does not get accepted the display will show FAIL and then change back to the Fault Screen Some of the parameters being displayed on a sub menu are long and switch betwee...

Страница 23: ...eparticular piece of equipment It also provides a means to clear the fault history Identification This sub menu item provides access to the model number and serial number optional for the particular p...

Страница 24: ...led Temperature HP BAL PNT OFF or 0 to 50 F in 5 F increments Available only for air handler heat pump systems Disables heat pump below the selected temperature Balance Point Temperature df BAL PNT OF...

Страница 25: ...horse power Diagnostics Sub menu Item Indication User Modifiable Options Comments Fault 1 FAULT 1 Most recent furnace fault For display only Fault 2 FAULT 2 Next most recent furnace fault For display...

Страница 26: ...number Optional Software SOFTWARE Displays application software revision Set up Sub menu Item User Modifiable Options Comments Heat Airflow Trim HT TRM 10 to 10 in 2 Incre ments Trims the heating airf...

Страница 27: ...tage AC unit Cool Airflow Profile CL PRFL A B C or D Selects the airflow profile for the non communicating 1 stage AC unit Cool ON Delay CL ON 5 10 20 or 30 seconds Selects the indoor blower on delay...

Страница 28: ...t most recent air handler fault For display only Fault 5 FAULT 5 Next most recent air handler fault For display only Fault 6 FAULT 6 Least recent air handler fault For display only Clear Fault History...

Страница 29: ...odifiable Options Comments Heat Airflow Trim HT TRM 10 to 10 in 2 Incre ments Trims the electric heating airflow by the selected amount Status Sub menu Item Indication for Display Only not User Modifi...

Страница 30: ...fault For display only Fault 2 FAULT 2 Next most recent AC HP fault For display only Fault 3 FAULT 3 Next most recent AC HP fault For display only Fault 4 FAULT 4 Next most recent AC HP fault For dis...

Страница 31: ...em User Modifiable Options Comments applies to AC and HP models Cool Airflow Trim CL TRM 10 to 10 in 2 Increments Selects the airflow trim amount applies to air conditioner only Cool Airflow Profile C...

Страница 32: ...Heat OFF Delay HT OFF 30 50 70 or 90 seconds 30 min default Selects the indoor blower off delay applies to heat pump only Defrost Interval DEFROST 30 60 90 or 120 min utes 30 min default Selects the...

Страница 33: ...INSTALLATION POWER UP SETUP USAGE GUIDE ADVANCED MENUS 33 NOTES...

Страница 34: ...means is also the installing contractor for the unit The warranty period begins on the date of the original installation Where the product is installed in a newly constructed home the date of the ins...

Страница 35: ...as described in the installation and operating manual 6 Replacement parts not supplied or designated by Goodman 7 Damage or repairs required as a result of any improper use maintenance operation or se...

Страница 36: ...nication Our continuing commitment to quality products may mean a change in specifications without notice 2009 Goodman Manufacturing Company L P Houston TX For complete information on Goodman warranti...

Отзывы: