GENERAL

Read carefully the instructions before installing this 

unit. Verify the technical characteristics of the motor in 

order to assure the compatibility with the device.

DESCRIPTION (diagram A)

This device is an electronic pump controller with in-

tegrated digital manometer an instantaneous lecture 

of the motor load. It manages the start and stop of a 

single-phase pump up to 2.2 kW (3 HP).

 

It can operate 

in  pflow  dependent  mode  or  in  pressostatic 

mode. The start pressure -and the stop pressure in 

pressostatic mode- are easily adjustable through the 

users control panel. 

This device protects the pump against overload 

(only 

DGplus and DGM2)

, minimal pressure and dry-running 

operation.

CLASSIFICATION AND TYPE

According to IEC 60730-1 and EN 60730-1 this unit 

is a control sensor device, electronic, independent 

assembly, with action type 1B (microdisconnection). 

Operating value: I <20% I learned. Pollution degree 2 

(clean environment) or flow>2,5 l/min. Rated impul

-

se voltage: cat II / 2500V. Temperatures for ball test: 

enclousure (75) and PCB (125). 

OPERATING CHARACTERISTICS (diagram C)

• 2 modes of operation: pressure dependent mode 

and pflow dependent mode.

• Adjustable start and stop pressure.

• Integrated digital pressure gauge with bar and psi 

indication.

• Inner pressure transmitter.

• Integrated non-return valve.

• 

Dry-running protection with led-light for flow 

indication.

• Protection against minimum pressure.

• Overcurrent protection with automatic restore 

attempts 

(only DGplus and DGM2)

.

• ART function (Automatic Reset Test). It can be 

enabled/disabled and set duration and number of 

attempts.

• APR function (Anti-blocking Periodic Routine). 

• 

Anti-flooding configuration.

• Manual start push-button (ENTER).

• Control panel with 3-digit display, LED indicator 

lights and push-buttons

• Volt-free contact for monitoring the alarms displa-

yed in the screen (only version A). 

• Stand-by mode.

TECHNICAL CHARACTERISTICS

• Rated motor power   

 

0,37-2,2KW

• Power supply 

 

   

~1 x 110-230Vac   

• 

Frequency    

 

 

50/60Hz

• 

Max. current 

  

 

16A, cos fi ≥ 0.6

• 

Protection degree    

 

IP65*

• 

Max. water temperature   

50ºC

• 

Max environment temperature  

60ºC

• 

Starting pressure range 

 

0,5÷7 bar

 

 

 

 

 

7÷102 psi

• 

Stop pressure  

 

 

1÷8 bar

     (P dependent mode) 

 

14÷116 psi

• 

Factory setting (START PRESSURE)  1,5 bar

• 

Max. operating pressure   

8 bar

• 

Hydraulic connection DIGIPLUS   G 1 1/4” M 

• 

Hydraulic connection DIGIMATIC   G 1” M 

• Net weight (without cables)  

1,3 kg

*Plugs and sockets built into the wiring of the 

device could modify the declared IP rating.
HIDRAULIC INSTALLATION

 

(diagram A)

  

Before proceeding with hydraulic connection 

it is essential to prime the pump correctly. This 

unit must be installed in a vertical position (arrows in 

upward position), thus connecting the inlet opening 

directly to the pump outlet; and the outlet to the 

network. The following accessories are recommended: 

flexible with a disassembling link for network protec

-

tion, protecting the set from possible flexion charges 

and vibrations, ball valve which permits the isolation 

of the pump from the net, a tap (A) at the same level 

of the unit FIG 1). 

In pressure dependent mode or in applications 

with cut-in pressures higher than 3 bar is compul-

sory the installation of a pneumatic tank.

ELECTRIC CONNECTION (diagram B)

  

The electric connection must be performed by 

qualified technicians in compliance with regu

-

lation of each country. Before doing manipulations 

inside the device, it must be disconnected from the 

electric supply.

Wrong connection could spoil the electronic circuit. 

The manufacturer declines all responsability in 

damages caused by wrong connections.

Check if power supply is beetween 110-230V.

If you have purchased the unit without cables follow 

diagram B:

• 

Use cables type H07RN-F 3G1 or 3G1,5 with section 

enough to the power installed:

• Do the pump connection U, V and  .

• Do the power supply connection

 

L, N and  .

• The earth conductor must be longer than the 

others. It will be the first one to be mounted during 

the assembly and the last one to be disconnected 

during the dismantling. 

The earth conductors 

connections are compulsory!

• Volt-free contact for monitoring the alarms displayed 

in the screen (only versions DGPLUS/DGM-A).

•  Maximum switching voltage: 250VAC / 220VDC.

• Maximum switching power: 62,5VA / 30W

CONTROL PANEL (diagram C)

The meanings of the different control panel elements 

are summarized on the following tables, where: 

• O means lit LED light.

• 

( ( O ) ) means slow-flashing.

DISPLAY

ACTION

OPERATION 

MODE

Is showed on screen instantaneous 

pressure or instantaneous current con-

sumption 

(only DGplus and DGM2)

.

ADJUSTMENT 

MODE

Is displayed on screen the adjusted 

start/stop pressure.

Is displayed the adjusted rated current.

ALARM MODE  Is displayed the alarm code.

STAND-BY 

MODE

Are displayed 3 flashing dots.

BASIC 

CONFIG.

Is displayed the sequence of basic con-

figuration parameters.

ADVANCED 

CONFIG.

Is displayed the sequence of advanced 

configuration parameters.

Содержание DIGIMATIC 1

Страница 1: ...INSTRUCTIONS MANUAL MANUAL DE INSTRUCCIONES MANUALE DI ISTRUZIONI MANUEL D UTILISATION BEDIENUNGSANLEITUNG DIGIPLUS DIGIMATIC 2 DIGIMATIC 1...

Страница 2: ...essione o all installazione Gefahr der Besch digung des Steuerger tes und der Druckleitungen und oder der gesamten Anlage Risk by electric shock Riesgo por choque el ctrico Risque d lectrocution Risch...

Страница 3: ...If Pressure dependent mode or P start 3 bar bar psi bar psi flow flow Amps A P STOP P STOP P START P START M B N O Outlet alarms Salida alarmas Sortie alarmes Uscita alarmi Ausgang alarms DIGIPLUS A...

Страница 4: ...C G 1 M Net weight without cables 1 3 kg Plugs and sockets built into the wiring of the device could modify the declared IP rating HIDRAULIC INSTALLATION diagram A Before proceeding with hydraulic con...

Страница 5: ...ssure view 3 Rated current adjustment STARTUP diagram C Before starting the device please read the pre vious sections especially Hydraulic Installation and Electrical connection Follow next steps 1 St...

Страница 6: ...tore the water supply After this first attempt are performed consecutive attempts every 30 minutes This function can be activated in the ADVANCED MENU It can also be set the number of attempts 1 48 an...

Страница 7: ...ion can also be restored manually by pressing ENTER O A04 O FAST CYCLING Hammering This alarm can be unabled or activated in the ADVANCED MENU The alarm is activated when 3 consecutive cycles occur in...

Страница 8: ...8 bar Conexi n red hidr ulica DIGIPLUS G 1 1 4 M Conexi n red hidr ulica DGMATIC G 1 M Peso neto sin cables 1 3 kg Los enchufes y conectores integrados en el ca bleado del aparato podr an modificar el...

Страница 9: ...aparato deber n leerse los apartados anteriores especialmente Instalaci n Hidr ulica y Conexi n el ctrica La puesta en marcha b sica consiste en 1 Poner en marcha el dispositivo pulsando 2 Configuraci...

Страница 10: ...restaurar el funcionamiento normal mediante una serie de puestas en marcha peri dicas Se realiza un primer intento a los 5 mi nutos Despu s de este primer intento se realizar n intentos sucesivos cad...

Страница 11: ...er restaurado manualmente pulsando ENTER O A04 O CICLOS R PIDOS S lo si la hemos activado en el MEN AVANZADO se activa la alarma cuando se producen tres ciclos consecutivos en un intervalo de tiempo e...

Страница 12: ...ydr DIGIPLUS G 11 4 M Raccordement hydr DIGIMATIC G 1 M Poids net sans c bles 1 3 kg Les prises et les connecteurs int gr s dans le c blage du dispositif peuvent modifier le degr de protection IP INST...

Страница 13: ...spositif en marche il faut consulter les paragraphes pr c dents notam ment Installation hydraulique et Raccordement lectrique La mise en marche de base consiste 1 Mettre en marche le dispositif en app...

Страница 14: ...ed marrer la pompe afin de r tablir l alimentation d eau Apr s cette premi re tentative sont effectu es des tentati ves cons cutives toutes les 30 minutes Cette fonction peut tre activ e dans le MENU...

Страница 15: ...appuyant sur ENTER O A04 O CYCLES RAPIDES Cette alarme peut tre d sactiv e ou activ e dans le MENU AVANC L alarme est activ e lorsque 3 cycles cons cutifs se produisent dans une plage inf rieure au te...

Страница 16: ...TIC G 1 M Pesso netto senza cavi 1 3 kg Le spine e i connettori integrati nel cablaggio del dispositivo potrebbero modificare il grado IP INSTALLAZIONE IDRAULICA schema A Prima di procedere alla conne...

Страница 17: ...ompa AVVIO schema C Prima di avviare l apparecchio dovranno essere letti i paragrafi precedenti specialmente quelli relativi a Installazione Idraulica e Connessione elettrica L avvio di base consiste...

Страница 18: ...la pompa per ripristinare l alimentazione idrica Dopo questo primo tentativo vengono eseguiti tenta tivi consecutivi ogni 30 minuti Questa funzione pu essere attivata nel MENU AVAN ZATO Si pu anche i...

Страница 19: ...funzionamento normale pu anche essere ripristinato manualmente premendo ENTER O A04 O CICLI ECCESSIVI Solo se l abbiamo attivato nel MENU AVANZATO si attiva l allarme quando si producono tre cicli con...

Страница 20: ...des Ger ts eingebaut sind k nnen die angegebene IP Schutzart ndern HYDRAULISCHE INSTALLATION Diagramm A Vor dem Anschluss berpr fen ob die Hydraulik der Pumpe ordnungsgem installiert wurde Die sollte...

Страница 21: ...n IGIMATIC 2 Einstellung der Stromst rke Dr cken Sie f r 3 Sekunden Die aktuell eingestellte Stromst rke wird auf dem Bildschirm angezeigt und die LED A blinkt Werk seinstellung 16A Mit den Tasten und...

Страница 22: ...chutzes A01 oder Mindestdruck A11 gestoppt hat ver sucht der ART nach 5 Minuten die Pumpe wieder zu starten um die Wasserversorgung wiederherzustellen Nach diesem ersten Versuch erfolgt alle 30 Minute...

Страница 23: ...arm kann im ERWEITERTEN MEN deaktiviert oder aktiviert werden Der Alarm wird aktiviert wenn 3 aufeinanderfolgende Zyklen in einem Bereich auftreten der niedriger ist als die eingestellte Zeit zwischen...

Страница 24: ...R ENTER 3 LED A 0 37 2 2 110 230 x 1 50 60 16 0 6 IP65 50 60 7 0 5 102 7 8 1 116 14 1 5 8 G 1 1 4 M DIGIPLUS G 1 M DIGIPLUS 1 3 IP 1 A 3 110 230 H07RN F 3G1 3G1 5 U V N L DGPLUS DGM A 250 220 30 62 5...

Страница 25: ...START O O P STOP O O FLOW O ALARM O O ON OFF configuration MENU ON OFF Pstop 3 CONFIG ADJUSTMENT 3 Pstart 3 CONFIG ADJUSTMENT 3 DGplus DGM2 3 1 DGM2 DGplus 2 3 16 LED A 1 3 3 LED START 3 7 0 5 4 LED S...

Страница 26: ...rc0 rc1 rc2 rc2 r01 r99 rc1 rc2 3 99 r03 H00 H99 H01 H00 H24 24 H00 rs0 rs1 rs1 rs0 ART A01 ALARM 5 ART A11 30 ADVANCED MENU 1 48 10 40 APR 72 10 APr 5 REGISTER rEC HF xxx 0 65535 HP xxx 0 65535 CF x...

Страница 27: ...NTER O ART 24 30 5 24 ENTER A11 O ADVANCED PROGRAMMING MENU A02 O DGM2 DGplus 4 ENTER O A04 O ADVANCED MENU 3 5 rc1 rc2 ENTER A05 O A30 O ADVANCED MENU ENTER Mbr O 200 000 200 400 600 800 Mbr ENTER O...

Страница 28: ...35 UE 2014 30 UE 2011 65 UE Normes EN 60730 2 6 EN 60730 1 EN 61000 6 1 EN 61000 6 3 CEI 60730 1 CEI 60730 2 6 DICHIARAZIONE DI CONFORMIT CE Dichiariamo sotto la nostra responsabilit che i materiali d...

Отзывы: