Microprocessed Voltage Regulator
Three-Phase Perfection Premium Series
User´s Manual
CM COMANDOS LINEARES
- 24/38 -
Triggered Bypass
KVA Surge
Output surge in KVA (beeps 2 times per second). Transfers to bypass
– does not
shut down the output.
Triggered Bypass
KW Surge
Output surge in KW (beeps 2 times per second). Transfers to bypass
– does not
shut down the output.
Triggered Bypass
Inrush KVA
Load peak in KVA above 125% (2 beeps per second). Transfers to bypass
– does
not shut down the output.
Triggered Bypass
Inrush KW
Load peak in KW above 125% (2 beeps per second). Transfers to bypass
– does
not shut down the output.
Output OFF
Frequency Below Limit
Input frequency 5% below the nominal (3 beeps per second). Shuts down the
output.
Output OFF
Freq. Above Limit
Input frequency 5% above the nominal (3 beeps per second). Shuts down the
output.
Output OFF
OVI Alarm
High output voltage, above the 10% range due to high input (3 beeps per second).
Shuts down the output.
Output OFF
UVI Alarm
Low output voltage, outside the 10% range due to the low input voltage (3 beeps
per second). Shuts down the output.