For specific information refer to the component manufacturer's
manual..
Maintenance
The inspection must be carried out by qualified service personnel.
Check the correct operation of the LEDs.
Check the correct functioning of the buzzer and relay.
Check the signal transmission to the central BMS / controller,
if connected.
Calibrate the sensor or contact the Manufacturer to exchange
the sensor with a factory calibrated sensor.
The sensors have an average life of 2 to 5 years, depending on
the type, after which they must be replaced.
Sensors must be checked after exposure to significant gas
concentrations, which can reduce sensor life and / or reduce
sensitivity.
10 REFRIGERANT LEAK DETECTOR